nal is applied on the control terminals and/or the bus, the fre-
quency converter starts.
NOTE: An active HAND-OFF-AUTO signal via digital inputs
has higher priority than the local control keys Hand On –Auto On.
The Reset key resets the frequency converter after an alarm (trip).
See Table 10 for a list of common VFD parameters.
Table 10 — Common VFD Parameters
Voltage
# of V's 2V 3V 4V 5V 6V 7V 8V
Drive Designation FVFD-1 FVFD-1 FVFD-1 FVFD-1 FVFD-2 FVFD-1 FVFD-2 FVFD-1 FVFD-2 FVFD-1 FVFD-2
# of Connected Fans 4 6 8 6 4 6 6 7 7 8 8
1-03 Torque
Characteristic
variable
torque
1 1 1 1 1 1 1 1 1 1 1
1-21 Motor Hp size
dependent
10 15 25.0 20.0 15.0 15 15 20 20 20 20
1-22 Motor Volts motor
dependent
REFER TO VOLTAGE SPECIFIC TABLE
1-23 Motor
Frequency
Hz 60 60 60 60 60 60 60 60 60 60 60
1-24 Motor
Amperage
size
dependent
REFER TO VOLTAGE SPECIFIC TABLE
1-25 Motor Rpm size
dependent
1130 1130 1130 1130 1130 1130 1130 1130 1130 1130 1130
1-73 Flying Restart NO 0 0 0 0 0 0 0 0 0 0 0
1-80 Function at
Stop
coast 0 0 0 0 0 0 0 0 0 0 0
1-90 Motor
Thermal
Protection
0 0 0 0 0 0 0 0 0 0 0 0
3-02 Min
Reference
Hz 0 0 0 0 0 0 0 0 0 0 0
3-03 Max
Reference
Hz 60 60 60 60 60 60 60 60 60 60 60
3-13 Type
Reference
remote 1 1 1 1 1 0 0 0 0 0 0
3-15 Src Ref#1 analog input 1 1 1 1 1 1 1 1 1 1 1
3-16 Src Ref#2 no function 0 0 0 0 0 0 0 0 0 0 0
3-41 Ramp Up s 20 20 20 20 20 20 20 20 20 20 20
3-42 Ramp Down s 20 20 20 20 20 20 20 20 20 20 20
4-10 Motor Speed
Direct
clockwise 0 0 0 0 0 0 0 0 0 0 0
4-12 Motor Speed
Low Limit
Hz 5 5 5 5 5 5 5 5 5 5 5
4-14 Motor Speed
High Limit
Hz 60 60 60 60 60 60 60 60 60 60 60
4-16 Torque Limit size
dependent
150 150 150 150 150 150 150 150 150 150 150
4-18 Current Limit size
dependent
110 110 110 110 110 110 110 110 110 110 110
4-19 Max Output
Frequency
Hz 61 61 61 61 61 61 61 61 61 61 61
5-10 Term#18 Di Start 8 8 8 8 8 8 8 8 8 8 8
5-12 Di #27 no function 0 0 0 0 0 2 2 2 2 2 2
5-
40 Relay 1 running 5 5 5 5 5 5 5 5 5 5 5
6-10 Term#53
Low V
0V 0 0 0 0 0 0 0 0 0 0 0
6-11 Term#53
High V
10V 10 10 10 10 10 10 10 10 10 10 10
8-01 Control Site digital 0 0 0 0 0 0 0 0 0 0 0
8-02 Control
Source
FC
port=RS485
1 1 1 1 1 1 1 1 1 1 1
8-03 Time Out
Time
s 10 10 10 10 10 10 10 10 10 10 10
8-04 Time Out
Function
stop 2 2 2 2 2 2 2 2 2 2 2
14-00 Pattern [Avm] 60AVM 0 0 0 0 0 0 0 0 0 0 0
14-01 Switching
Frequency
4kHz 6 6 6 6 6 6 6 6 6 6 6