EasyManua.ls Logo

Carrier 160 Series - Electrical Connections

Carrier 160 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58CV
Install
a
sediment
trap
in
riser
leading
to
furnace
as
shown
in
Fig.
22.
Connect
a
capped
nipple
into
lower
end
of
tee.
Capped
nipple
should
extend
below
level
of
furnace
gas
controls.
Place
a
ground
joint
union
between
furnace
gas
control
vaive
and
exterior
manual
equipment
gas
shutoff
valve.
A
1/8-in.
(3
mm)
NPT
plugged
tapping,
accessible
for
test
gauge
connection,
MUST
be
installed
immediately
upstream
of
gas
supply
connection
to
furnace
and
downstream
of
manual
equipment
shutoff
valve.
Piping
should
be
pressure
and
leak
tested
in
accordance
with
the
current
addition
of
the
NFGC
in
the
United
States,
local,
and
national
plumbing
and
gas
codes
before
the
furnace
has
been
connected.
After
all
connections
have
been
made,
purge
lines
and
check
for
leakage
at
furnace
prior
to
operating
furnace.
If
pressure
exceeds
0.5
psig
(14-In.
W.C.),
gas
supply
pipe
must
be
disconnected
from
furnace
and
capped
before
and
during
supply
pipe
pressure
test.
If
test
pressure
is
equal
to
or
less
than
0.5
psig
(14-In.
W.C.),
turn
off
electric
shutoff
switch
located
on
furnace
gas
control
valve
and
accessible
manual
equipment
shutoff
valve
before
and
during
supply
pipe
pressure
test.
After
all
connections
have
been
made,
purge
lines
and
check
for
leakage
at
furnace
prior
to
operating
furnace.
The
gas
supply
pressure
shall
be
within
the
maximum
and
minimum
inlet
supply
pressures
marked
on
the
rating
plate
with
the
furnace
burners
ON
and
OFF,
TOP
VIEW
OF
BURNER
AND
MANIFOLD
ASSEMBLY
90°
Elbow
—_,
2
°
To
Gas
°
1]
Suppl
/
5
upply
2"(51mm)
Nipple
/
}
Street
Elbow
Gas
Valve
A08551
Fig.
21
-
Burner
and
Manifold
GAS
—_—_——_—_—EV
SUPPLY
=———_—_—
eo
MANUAL
a
SHUTOFF
_
_
VALVE
(REQUIRED)
SEDIMENT
a
TRAP
UNION
A02085
Fig.
22
-
Typical
Gas
Pipe
Arrangement
ELECTRICAL
CONNECTIONS
CE
UA
Le:
ELECTRICAL
SHOCK
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death.
Blower
access
panel
door
switch
opens
115-v
power
to
control.
No
component
operation
can
occur.
Do
not
bypass
or
close
switch
with panel
removed.
See
Fig.
25
for
field
wiring
diagram
showing
typical
field
115-v
wiring.
Check
all
factory
and
field
electrical
connections
for
tightness.
Field-supplied
wiring
shall
conform
with
the
limitations
of
63°F
(33°C)
rise.
4
WARNING
ELECTRICAL
SHOCK
AND
FIRE
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
or
property
damage.
The
cabinet
MUST
have
an
uninterrupted
or
unbroken
ground
according
to
NEC
ANSI/NFPA
70-2011
or
local
codes
to
minimize
personal
injury
if
an
electrical
fault
should
occur.
This
may
consist
of
electrical
wire,
conduit
approved
for
electrical
ground
or
a
listed,
grounded
power
cord
(where
permitted
by
local
code)
when
installed
in
accordance
with
existing
electrical
codes.
Refer
to
the
power
cord
manufacturer’s
ratings
for
proper
wire
gauge.
Do
not
use gas
piping
as
an
electrical
ground.
FURNACE
MAY
NOT
OPERATE
HAZARD
Failure
to
follow
this
caution
may
result
in
intermittent
furnace
operation.
Furnace
control
must
be
grounded
for
proper
operation
or
else
control
will
lock
out.
Control
must
remain
grounded
through
green/yellow
wire
routed
to
gas
valve
and
manifold
bracket
screw.
115-V
Wiring
Verify
that
the
voltage,
frequency,
and
phase
correspond
to
that
specified
on
unit
rating
plate.
Also,
check
to
be
sure
that
service
provided
by
utility
is
sufficient
to
handle
load
imposed
by
this
equipment.
Refer
to
rating
plate
or
Table
7
for
equipment
electrical
specifications.
U.S.
Installations:
Make
all
electrical
connections
in
accordance
with
National
Electrical
Code
(NEC)
ANSI/NFPA
70-2011
and
any
local
codes
or
ordinances
that
might
apply.

Related product manuals