EasyManua.ls Logo

Carrier 160 Series - Gas Piping

Carrier 160 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Return
Air
Connections
CA
AUN
LO:
FIRE
HAZARD
A
failure
to
follow
this
warning
could
cause
personal
injury,
death
and/or
property
damage.
Never
connect
return-air
ducts
to
the
back
of
the
furnace.
Follow
instructions
below.
Downflow
Furnaces
The
return-air
duct
must
be
connected
to
return-air
opening
(bottom
inlet)
as
shown
in
Fig.
3.
DO
NOT
cut
into
casing
sides
(left
or
right).
Side
opening
is
permitted
for
only
upflow
and
certain
horizontal
furnaces.
Bypass
humidifier
connections
should
be
made
at
ductwork
or
coil
casing
sides
exterior
to
furnace.
(See
Fig.
19.)
Uptlow and
Horizontal
Furnaces
The
return-air
duct
must
be
connected
to
bottom,
sides
(left
or
right),
or
a
combination
of
bottom
and
side(s)
of
main
furnace
casing
as
shown
in
Fig.
3.
Bypass
humidifier
may
be
attached
into
unused
return
air
side
of
the
furnace
casing.
(See
Fig.
18
and
20.)
Not
all
horizontal
furnace
models
are
approved
for
side
return
air
connections.
(See
Fig.
20.)
GAS
PIPING
CUANDO:
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Never
purge
a
gas
line
into
a
combustion
chamber.
Never
test
for
gas
leaks
with
an
open
flame.
Use
a
commercially
available
soap
solution
made
specifically
for
the
detection
of
leaks
to
check
all
connections.
A
fire
or
explosion
may
result
causing
property
damage,
personal
injury
or
loss
of
life.
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Use
proper
length
of
pipe
to
avoid
stress
on
gas
control
manifold
and
a
gas
leak.
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Gas
valve
inlet
and/or
inlet
pipe
must
remain
capped
until
gas
supply
line
is
permanently
installed
to
protect
the
valve
from
moisture
and
debris.
Also,
install
a
sediment
trap
in
the
gas
supply
piping
at
the
inlet
to
the
gas
valve.
Gas
piping
must
be
installed
in
accordance
with national
and
local
codes.
Refer
to
current
edition
of
NFGC
in
the
U.S.
Installations
must
be
made
in
accordance
with
all
authorities
having
jurisdiction.
If
possible,
the
gas
supply
line
should
be
a
separate
line
running
directly
from
meter
to
furnace.
NOTE:
In
the
state of
Massachusetts:
1.
Gas
supply
connections
MUST
be
performed
by
a
li-
censed
plumber
or
gas
fitter.
bo
.
When
flexible
connectors
are
used,
the
maximum
length
shall
not
exceed
36
in.
(915
mm).
3.
When
lever
handle
type
manual
equipment
shutoff
valves
are
used,
they
shall
be
T-handle
valves.
4,
The
use
of
copper
tubing
for
gas
piping
is
NOT
approved
by
the
state of
Massachusetts.
Refer
to
Table
6
for
recommended
gas
pipe
sizing.
Risers
must
be
used
to
connect
to
furnace
and
to
meter.
Support
all
gas
piping
with
appropriate
straps,
hangers,
etc.
Use
a
minimum
of
1
hanger
every
6
ft.
(1.8
M).
Joint
compound
(pipe
dope)
should
be
applied
sparingly
and
only
to
male
threads
of
joints.
Pipe
dope
must
be
resistant
to
the
action
of
propane
gas.
Table
6
-
Maximum
Capacity
of
Pipe
NOMINAL
LENGTH
OF
PIPE
FT
(M)
INTERNAL
ROME
;
1
cata
10
20 30 40 50
IN.
(MIM)
-
(MM)
(3.0)
|
(6.0)
|
(4)
|
(12.4)
|
(15.2)
17212.)
|
0.622(158)
175
|
120
o7 a2
73
3/4
(49.0)
|
0.824(209)
|
360
|
250
|
200
170
151
1(25.4)
|
1.049(268)
|
680
|
465
|
375 320
|
285
1-4/4
G18)
1.380
(35.0)
|
1400
|
950
|
770 seo
|
580
6a)
1.610
(40.9)
|
2100
|
1460
|
1180
|
990 900
*
Cubic
f
of
gas
per
hr
for
gas
pressures
of
0.5
psig
(14-In.
W.C.)
or
less
and
a
pressure
drop
of
0.5-In.
W.C.
(based
on
a
0.60
specific
gravity
gas).
Ref:
Table
6
and
9.2
NFGC.
4
WARNING
FIRE
OR
EXPLOSION
HAZARD
A
failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
If
local
codes
allow
the
use
of
a
flexible
gas
appliance
connector,
always
use
a
new
listed
connector.
Do
not
use
a
connector
which
has
previously
served
another
gas
appliance.
Black
iron
pipe
shail
be
installed
at
the
furnace
gas
control
valve
and
extend
a
minimum
of
2-in.
(51
mm)
outside
the
furnace.
FURNACE
DAMAGE
HAZARD
Failure
to
follow
this
caution
may
result
in
furnace
damage.
Connect
gas
pipe
to
furnace
using
a
backup
wrench
to
avoid
damaging
gas
controls
and
burner
misalignment.
An
accessible
manual
equipment
shutoff
valve
MUST
be
installed
external
to
furnace
casing
and
within
6
ft.
(1.8
M)
of
furnace.
A
1/8-in.
(3
mm)
NPT
plugged
tapping,
accessible
for
test
gauge
connection,
MUST
be
installed
immediately
upstream
of
gas
supply
connection
to
furnace
and
downstream
of
manual
equipment
shutoff
vaive.
NOTE:
The
furnace
gas
control
valve
inlet
pressure
tap
connection
is
suitable
to
use
as
test
gauge
connection
providing
test
pressure
DOES
NOT
exceed
maximum
0.5
psig
(14-In.
W.C.)
stated
on
gas
control
valve.
(See
Fig.
50.)
Some
installations
require
gas
entry
on
right
side
of
furnace
(as
viewed
in
upflow).
(See
Fig.
21.)
19
58CV

Related product manuals