EasyManua.ls Logo

Carrier 160 Series - Page 22

Carrier 160 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58CV
AI0144
Fig.
24
-
Field-Supplied
Electrical
Box
on
Furnace
Casing
Power
Cord
Installation
in
Furnace
J-Box
NOTE:
Power
cords
must
be
able
to
handle
the
electrical
requirements
listed
in
Table
6.
Refer
to
power
cord
manufacturer’s
listings.
1.
Remove
cover
from
J-Box.
2.
Route
listed
power
cord
through
7/8-in.
(22
mm)
diameter
hole
in
J-Box.
3.
Secure
power
cord
to
J-Box
bracket
with
a
strain
relief
bushing
or
a
connector
approved
for
the
type
of
cord
used.
4.
Secure
field
ground
wire
to
green
ground
screw
on
J-Box
bracket.
5,
Connect
line
voltage
leads
as
shown
in
Fig.
25.
6.
Reinstall
cover
to
J-Box.
Do
not
pinch
wires
between
cover
and
bracket.
BX
Cable
Installation
in
Furnace
J-Box
1.
Remove
cover
from
J-Box.
bo
bo
bo
.
Route
BX
cable
into
7/8-in.
(22
mm)
diameter
hole
in
J-Box.
3.
Secure
BX
cable
to
J-Box
bracket
with
connectors
ap-
proved
for
the
type
of
cable
used.
4.
Secure
field
ground
wire
to
green
ground
screw
on
J-Box
bracket.
5,
Connect
line
voltage
leads
as
shown
in
Fig.
25.
6.
Reinstall
cover
to
J-Box.
Do
not
pinch
wires
between
cover
and
bracket.
24-V
Wiring
Make
field
24-v
connections
at
the
24-v
terminal
strip.
(See
Fig.
25
-
34.)
Connect
terminal
Y/Y2
as
shown
in
Fig.
27-34
for
proper
cooling
operation.
Use
only
AWG
No.
18,
color-coded,
copper
thermostat
wire.
The
24-v
circuit
contains
an
automotive-type,
3-amp.
fuse
located
on
the
control.
Any
direct
shorts
during
installation,
service,
or
maintenance
could
cause
this
fuse
to
blow.
If
fuse
replacement
is
required,
use
ONLY
a
3-amp.
fuse
of
identical
size.
ACCESSORIES
1.
Electronic
Air
Cleaner
(EAC)
Connect
an
accessory
Electronic
Air
Cleaner
(if
used)
us-
ing
1/4-in
female
quick
connect
terminals
to
the
two
male
1/4-in
quick-connect
terminals
on
the
control
board
marked
EAC-1
and
EAC-2.
The
terminals
are
rated
for
11SVAC,
1.0
amps
maximum
and
are
energized
during
blower
motor
operation.
(See
Fig.
26.)
.
Humidifier
(HUM)
Connect
an
accessory
24
VAC,
0.5
amp.
maximum
hu-
midifier
(if
used)
to
the
1/4-in
male
quick-connect
HUM
terminal
and
COM-24V
screw
terminal
on
the
control
board
thermostat
strip.
The
HUM
terminal
is
energized
when
blower
is
energized
in
heating.
(See
Fig.
26.)
NOTE:
DO
NOT
connect
furnace
control
HUM
terminal
to
HUM
(humidifier)
terminal
on
Thermidistat,
Zone
Controller
or
similar
device.
See
Thermidistat©,
Zone
Controller,
thermostat,
or
controller
manufacturer’s
instructions
for
proper
connection.
VENTING
The
furnace
shall
be
connected
to
a
listed
factory
built
chimney
or
vent,
or
a
clay-tile
lined
masonry
or
concrete
chimney.
Venting
into
an
unlined
masonry chimney
or
concrete
chimney
is
prohibited.
When
an
existing
Category
I
furnace
is
removed
or
replaced,
the
original
venting
system,
may
no
longer
be
sized
to
properly
vent
the
attached
appliances.
An
improperly
sized
Category
I
venting
system
could
cause
the
formation
of
condensate
in
the
furnace
and
vent,
leakage
of
condensate
and
combustion
products,
and
spillage
of
combustion
products
into
the
living
space.
bo

Related product manuals