EasyManua.ls Logo

Carrier 160 Series - Check Safety Controls; Check Main Limit Switch; Check Draft Safeguard Switch; Check Pressure Switch(es)

Carrier 160 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58CV
Check
Safety
Controls
The
flame
sensor,
gas
valve,
and
pressure
switch
were
all
checked
in
the
Start-up
procedure
section
as
part
of
normal
operation.
1.
Check
Main
Limit
Switch
This
control
shuts
off
combustion
system
and
energizes
air-circulating
blower
motor,
if
furnace
overheats.
By
us-
ing
this
method
to
check
limit
control,
it
can
be
established
that
limit
is
functioning
properly
and
will
operate
if
there
is
a
restricted
return-air
supply
or
motor
failure.
If
limit
control
does
not
function
during
this
test,
cause
must
be
determined
and
corrected.
a.
Run
furnace
for
at
least
5
minutes.
b.
Gradually
block
off
return
air
with
a
piece
of
card-
board
or
sheet
metal
until
the
limit
trips.
c.
Unblock
return
air
to
permit
normal
circulation.
d.
Burners
will
re-light
when
furnace
cools
down.
1)
Check
draft
safeguard
switch.
The
purpose
of
this
control
is
to
cause
the
safe
shutdown
of
the
furnace
during
certain
blocked
vent
conditions.
a.
Verify
vent
pipe
is
cool
to
the
touch.
b.
Disconnect
power
to
furnace
and
remove
vent
con-
nector
from
furnace
vent
elbow.
c.
Restore
power
to
furnace
and
set
room
thermostat
above
room
temperature.
d.
After
normal
start-up,
allow
furnace
to
operate
for
2
minutes,
then
block
vent
elbow
in
furnace
80
percent
of
vent
area
with
a
piece
of
flat
sheet
metal.
e.
Furnace
should
cycle
off
within
2
minutes.
If
gas
does
not
shut
off
within
2
minutes,
determine
reason
draft
safeguard
switch
did not
function
properly
and
correct
condition.
f.
Remove
blockage
from
furnace
vent
elbow.
g.
Switch
will
auto-reset
when
it
cools.
h.
Re-install
vent
connector.
NOTE:
Should
switch
remain
open
longer
than
3
minutes,
furnace
control
board
will
lockout
the
furnace
for
3
hours.
To
reset
furnace
control
board,
turn
thermostat
below
room
temperature
or
from
HEAT
to
OFF
and
turn
115-v
power
OFF,
then
back
ON.
3.
Check
Pressure
Switch(es)
This
control
proves
operation
of
the
draft
inducer
blower.
a.
Turn
off
115-v
power
to
furnace.
b.
Disconnect
inducer
motor
lead
wires
from
wire
har-
ness.
c.
Turn
on
115-v
power
to
furnace.
d.
Set
thermostat
to
“call
for
heat”
and
wait
1
minute.
When
pressure
switch
is
functioning
properly,
hot
sur-
face
igniter
should
NOT
glow
and
control
diagnostic
light
flashes
a
status
code
32.
If
hot
surface
igniter
glows
when
inducer
motor
is
disconnected,
shut
down
furnace
immediately.
e.
Determine
reason
pressure
switch
did not
function
properly
and
correct
condition.
f.
Turn
off
115-v
power
to
furnace.
g.
Reconnect
inducer
motor
wires,
replace
outer
door,
and
turn
on
115-v
power.
h.
Blower
will
run
for
90
seconds
before
beginning
the
call
for
heat
again.
i.
Furnace
should
ignite
normally.
Checklist
1.
Put
away
tools
and
instruments.
Clean
up
debris.
2.
Verity
that
switches
SW1-1
and
SW1-6
are
OFF
and
oth-
er
setup
switches
are
set
as
desired.
Verity
that
switches
SW1-7
and
SW1-8
for
the
blower
OFF
DELAY
are
set
as
desired
per
Table
10.
3.
Verity
that
blower
and
burner
access
doors
are
properly
in-
stalled.
4.
Cycle
test
furnace
with
room
thermostat.
5.
Check
operation
of
accessories
per
manufacturer’s
instruc-
tions.
6.
Review
User’s
Guide
with
owner.
7.
Attach
literature
packet
to
furnace.
SERVICE
AND
MAINTENANCE
PROCEDURES
CA
AUN
LO:
FIRE,
INJURY
OR
DEATH
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death
and/or
property
damage.
The
ability
to
properly
perform
maintenance
on_
this
equipment
requires
certain
knowledge,
mechanical
skills,
tools,
and
equipment.
If
you
do
not
possess
these,
do
not
attempt
to
perform
any
maintenance
on
this
equipment
other
than
those
procedures
recommended
in
the
User’s
Manual.
4&
CAUTION
ENVIRONMENTAL
HAZARD
Failure
to
follow
this
caution
may
result
in
environmental
pollution.
Remove
and
recycle
all
components
or
materials
(i.e.
oil,
refrigerant,
control
board,
etc.)
before
unit
final
disposal.
ELECTRICAL
SHOCK,
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury
or
death,
or
property
damage.
Before
installing,
modifying,
or
servicing
system,
main
electrical
disconnect
switch
must
be
in
the
OFF
position
and
install
a
lockout
tag.
There
may
be
more
than
one
disconnect
switch.
Lock
out
and
tag
switch
with
a
suitable
warning
label.
Verify
proper
operation
after
servicing.
ELECTRICAL
OPERATION
HAZARD
Failure
to
follow
this
caution
may
result
in
improper
furnace
operation
or
failure
of
furnace.
Label
all
wires
prior
to
disconnection
when
servicing
controls.
Wiring
errors
can
cause
improper
and
dangerous
operation.
General
These
instructions
are
written
as
if
the
furnace
is
installed
in
an
upflow
application.
An
upflow
furnace
application
is
where
the
blower
is
located
below
the
combustion
and
controls
section
of
46

Related product manuals