EasyManua.ls Logo

Carrier 160 Series - Sequence of Operation; Two-Stage Heating (Adaptive Mode) with Single-Stage Thermostat; Two-Stage Thermostat and Two-Stage Heating; Cooling Mode Operation

Carrier 160 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
13.
Reconnect
wires
to
the
following
components
(Use
con-
nection
diagram
on
wiring
label,
if
wires
were
not
marked
for
reconnection
locations.):
a.
Draft
safeguard
switch.
b.
Inducer
motor.
.
Pressure
switches.
.
Limit
overtemperature
switch.
.
Gas
valve.
.
Hot
surface
igniter.
.
Flame-sensing
electrode.
>
wo mo
.
Flame
rollout
switches.
14.
Reinstall
internal
vent
pipe,
if
applicable.
15.
Reinstall
vent
connector
on
furnace
vent
elbow.
Securely
fasten
vent
connector
to
vent
elbow
with
2
field-supplied,
corrosion-resistant,
sheet
metal
screws
located
180°
apart.
16.
Replace
blower
access
door
only
if
it
was
removed.
17.
Set
thermostat
above
room
temperature
and
check
furnace
for
proper
operation.
18.
Verify
blower
airflow
and
speed
changes
between
heating
and
cooling.
4
WARNING
FIRE
OR
EXPLOSION
HAZARD
Failure
to
follow
this
warning
could
result
in
personal
injury,
death,
and/or
property
damage.
Never
purge
a
gas
line
into
a
combustion
chamber.
Never
test
for
gas
leaks
with
an
open
flame.
Use
a
commercially
available
soap
solution
made
specifically
for
the
detection
of
leaks
to
check
all
connections.
A
fire
or
explosion
may
result
causing
property
damage,
personal
injury
or
loss
of
life.
19.
Check
for
gas
leaks.
Sequence
of
Operation
NOTE:
Furnace
control
must
be
grounded
for
proper
operation
or
else
control
will
lock
out.
Control
is
grounded
through
green/yellow
wire
routed
to
gas
valve
and
burner
box
screw.
Using
the
schematic
diagram
in
Fig.
53,
follow
the
sequence
of
operation
through
the
different
modes.
Read
and
follow
the
wiring
diagram
very
carefully.
NOTE:
If
a
power
interruption
occurs
during
a
call
for
heat
(W/W1
or
W/W1-and-W2),
the
control
will
start
a
90-second
blower-only
ON
period
two
seconds
after
power
is
restored,
if
the
thermostat
is
still
calling
for
gas
heating.
The
amber
LED
light
will
flash
code
12
during
the
90-second
period,
after
which
the
LED
will
be
ON
continuous,
as
long
as
no
faults
are
detected.
After
the
90-second
period,
the
furnace
will
respond
to
the
thermostat
normally.
The
blower
door
must
be
installed
for
power
to
be
conducted
through
the
blower
door
interlock
switch
ILK
to
the
furnace
control
CPU,
transformer
TRAN,
inducer
motor
IDM,
blower
motor
BLWM,
hot-surface
igniter
HSI,
and
gas
vaive
GV.
1.
Two-Stage
Heating
(Adaptive
Mode)
with
Single-Stage
Thermostat
See
Fig.
27
-
34
for
thermostat
connections
NOTE:
The
low-heat
only
switch
SW1-2
selects
either
the
low-heat
only
operation
mode
when
ON,
(see
item
2.
below)
or
the
adaptive
heating
mode
when
OFF
in
response
to
a
call
for
heat.
(See
Table
10.)
When
the
W2
thermostat
terminal
is
energized
it
will
always
cause
high-heat
operation
when
the
R-to-W
circuit
is
closed,
regardless
of
the
setting
of
the
low-heat
only
switch.
This
furnace
can
operate
as
a
two-stage
furnace
with
a
single-stage
thermostat
because
the
furnace
control
CPU
includes
a
programmed
adaptive
sequence
of
controlled
operation,
which
selects
low-heat
or
high-heat
operation.
This
selection
is
based
upon
the
stored
history
of
the
length
of
previous
gas-heating
periods
of
the
single-stage
thermostat.
The
furnace
will
start
up
in
either
low-
or
high-heat.
If
the
furnace
starts
up
in
low-heat,
the
control
CPU
determines
the
low-heat
on-time
(from
0
to
16
minutes)
which
is
permitted
before
switching
to
high-heat.
If
the
power
is
interrupted,
the
stored
history
is
erased
and
the
control
CPU
will
select
low-heat
for
up
to
16
minutes
and
then
switch
to
high-heat,
as
long
as
the
thermostat
continues
to
call
for
heat.
Subsequent
selection
is
based
on
stored
history
of
the
thermostat
cycle
times.
The
wail
thermostat
“calls
for
heat”,
closing
the
R-to-W
circuit.
The
furnace
control
performs
a
self-check,
verifies
the
low-heat
and
high-heat
pressure
switch
contacts
LPS
and
HPS
are
open,
and
starts
the
inducer
motor
IDM
in
high-speed.
a.
Inducer
Prepurge
Period
(1.)
If
the
furnace
control
CPU
selects
low-heat
oper-
ation
the
inducer
motor
IDM
comes
up
to
speed,
the
low-heat
pressure
switch
LPS
closes,
and
the
furnace
control
CPU
begins
a
15-second
prepur-
ge
period.
If
the
low-heat
pressure
switch
LPS
fails
to
remain
closed
the
inducer
motor
IDM
will
remain
running
at
high-speed.
After
the
low-heat
pressure
switch
re-closes
the
furnace
control
CPU
will
begin
a
15-second
prepurge
period,
and
con-
tinue
to
run
the
inducer
motor
IDM
at
high-
speed.
(2.)
If
the
furnace
control
CPU
selects
high-heat
op-
eration,
the
inducer
motor
IDM
remains
running
at
high-speed,
and
the
high-heat
pressure
switch
relay
HPSR
is
de-energized
to
close
the
NC
con-
tact.
When
sufficient
pressure
is
available
the
high-heat
pressure
switch
HPS
closes,
and
the
high-heat
gas
valve
solenoid
GV-HI
is
ener-
gized.
The
furnace
control
CPU
begins
a
15-second
prepurge
period
after
the
low-heat
pressure
switch
LPS
closes.
If
the
high-heat
pres-
sure
switch
HPS
fails
to
close
and
the
low-heat
pressure
switch
LPS
closes,
the
furnace
will
oper-
ate
at
low-heat
gas
flow
rate
until
the
high-heat
pressure
switch
closes
for
a
maximum
of
2
min-
utes
after
ignition.
b.
Igniter
Warm-Up
-At
the
end
of
the
prepurge
period,
the
Hot-Surface
Igniter
HSI
is
energized
for
a
17-second
igniter
warm-up
period.
c.
Trial-For-Ignition
Sequence
-When
the
igniter
warm-up
period
is
completed
the
main
gas
valve
relay
contact
GVR
closes
to
energize
the
gas
valve
solenoid
GV-M.
The
gas
valve
solenoid
GV-M
permits
gas
flow
to
the
burners
where
it
is
ignited
by
the
HSI.
Five
seconds
after
the
GVR
closes,
a
2-second
flame
prov-
ing
period
begins.
The
HSI
igniter
will
remain
ener-
gized
until
the
flame
is
sensed
or
until
the
2-second
flame
proving
period
begins.
If
the
furnace
control
CPU
selects
high-heat
operation,
the
high-heat
gas
valve
solenoid
GV-HI
is
also
energized.
31
58CV

Related product manuals