EasyManua.ls Logo

Carrier 160 Series - Single-Stage Cooling Operation; Single-Stage Thermostat & Two-Speed Cooling (Adaptive); Two-Stage Thermostat & Two-Speed Cooling; Thermidistat Mode Operation

Carrier 160 Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
etc.).
If
flame
is
proved
when
flame
should
not
be
present,
the
furnace
control
CPU
will
lock
out
of
Gas-
Heating
mode
and
operate
the
inducer
motor
IDM
on
high
speed
until
flame
is
no
longer
proved.
e.
Blower-On
delay
-
If
the
burner
flame
is
proven
the
blower-ON
delays
for
low-heat
and
high-heat
are
as
follows:
Low-heat
-
45
seconds
after
the
gas
valve
GV-M
is
opened
the
blower
motor
BLWM
is
turned
ON
at
low-heat
airflow.
High-heat
-
25
seconds
after
the
gas
valve
GV-M
is
opened
the
BLWM
is
turned
ON
at
high-heat
airflow.
Simultaneously,
the
humidifier
terminal
HUM
and
electronic
air
cleaner
terminal
EAC-1
are
energized
and
remain
energized
throughout
the
heating
cycle.
f.
Switching
from
Low-
to
High-Heat
-
If
the
furnace
control
CPU
switches
from
low-heat
to
high-heat,
the
furnace
control
CPU
will
switch
the
inducer
motor
IDM
speed
from
low
to
high.
The
high-heat
pressure
switch
relay
HPSR
is
de-energized
to
close
the
NC
contact.
When
sufficient
pressure
is
available
the
high-
heat
pressure
switch
HPS
closes,
and
the
high-heat
gas
valve
solenoid
GV-HI
is
energized.
The
blower
motor
BLWM
will
transition
to
high-heat
airflow
five
seconds
after
the
furnace
control
CPU
switches
from
low-heat
to
high-heat.
g.
Switching
from
High-
to
Low-Heat
-The
furnace
control
CPU
will
not
switch
from
high-heat
to
low-
heat
while
the
thermostat
R-to-W
circuit
is
closed
when
using
a
single-stage
thermostat.
h.
Blower-Off
Delay
-When
the
thermostat
is
satisfied,
the
R
to
W
circuit
is
opened,
de-energizing
the
gas
valve
GV-M,
stopping
gas
flow
to
the
burners,
and
de-energizing
the
humidifier
terminal
HUM.
The
in-
ducer
motor
IDM
will
remain
energized
for
a
5-second
post-purge
period.
The
blower
motor
BLWM
and
air
cleaner
terminal
EAC-1
will
remain
energized
at
low-heat
airflow
or
transition
to
low-heat
airflow
for
90,
120, 150,
or
180
seconds
(depending
on
selection
at
blower-OFF
delay
switches).
The
fur-
nace
control
CPU
is
factory-set
for
a
120-second
blower-OFF
delay.
2.
Two-Stage
Thermostat
and
Two-Stage
Heating
See
Fig.
27-34
for
thermostat
connections.
NOTE:
In
this
mode
the
low-heat
only
switch
SW1-2
must
be
ON
to
select
the
low-heat
only
operation
mode
in
response
to
closing
the
thermostat
R-to-W1
circuit.
Closing
the
thermostat
R-to-
W1-and-W2
circuits
always
causes
high-heat
operation,
regardless
of
the
setting
of
the
low-heat
only
switch.
The
wall
thermostat
“calls
for
heat”,
closing
the
R-to-W1
circuit
for
low-heat
or
closing
the
R-to-W1-and-W2
circuits
for
high-heat.
The
furnace
control
performs
a
self-check,
verifies
the
low-heat
and
high-heat
pressure
switch
contacts
LPS
and
HPS
are
open,
and
starts
the
inducer
motor
IDM
in
high-speed.
The
start
up
and
shut
down
functions
and
delays
described
in
item
1.
above
apply
to
the
2-stage
heating
mode
as
well,
except
for
switching
from
low-
to
high-Heat
and
vice versa.
a.
Switching
from
Low-
to
High-Heat
-
If
the
thermo-
stat
R-to-W1
circuit
is
closed
and
the
R-to-W2
cir-
cuit
closes,
the
furnace
contro!
CPU
will
switch
the
inducer
motor
IDM
speed
from
low
to
high.
The
high-heat
pressure
switch
relay
HPSR
is
de-energized
to
close
the
NC
contact.
When
sufficient
pressure
is
available
the
high-heat
pressure
switch
HPS
closes,
and
the
high-heat
gas
valve
solenoid
GV-HI
is
ener-
gized.
The
blower
motor
BLWM
will
transition
to
high-heat
airflow
five
seconds
after
the
R-to-W2
cir-
cuit
closes.
b.
Switching
from
High-
to
Low-Heat
-If
the
thermo-
stat
R-to-
W2
circuit
opens,
and
the
R-to-W1
circuit
remains
closed,
the
furnace
control
CPU
will
switch
the
inducer
motor
IDM
speed
from
high
to
low.
The
high-heat
pressure
switch
relay
HPSR
is
energized
to
open
the
NC
contact
and
de-energize
the
high-heat
gas
valve
solenoid
GV-HI.
When
the
inducer
motor
IDM
reduces
pressure
sufficiently,
the
high-heat
pres-
sure
switch
HPS
will
open.
The
gas
valve
solenoid
GV-M
will
remain
energized
as
long
as
the
low-heat
pressure
switch
LPS
remains
closed.
The
blower
motor
BLWM
will
transition
to
low-heat
airflow
five
seconds
after
the
R-to-W2
circuit
opens.
3.
Cooling
mode
The
thermostat
“calls
for
cooling”.
a.
Single-Speed
Cooling-
See
Fig.
27
for
thermostat
connections
The
thermostat
closes
the
R-to-G-and-Y
circuits.
The
R-to-
Y
circuit
starts
the
outdoor
unit,
and
the
R-to-
G-and-Y/Y2
circuits
start
the
furnace
blower
motor
BLWM
on
cooling
airflow.
Cooling
airflow
is
based
on
the
A/C
selection
shown
in
Fig.
57.
The
electronic
air
cleaner
terminal
EAC-1
is
energized
with
115
vac
when
the
blower
motor
BLWM
is
operating.
When
the
thermostat
is
satisfied,
the
R-to-G-and-Y
circuits
are
opened.
The
outdoor
unit will
stop,
and
the
furnace
blower
motor
BLWM
will
continue
operating
at
cooling
airflow
for
an
additional
90
seconds.
Jump-
er
Y/Y2
to
DHUM
to
reduce
the
cooling
off-delay
to
5
seconds.
(See
Fig.
26.)
b.
Single-Stage
Thermostat
and
Two-Speed
Cooling
(Adaptive
Mode)
-
See
Fig.
34
for
thermostat
connections.
This
furnace
can
operate
a
two-speed
cooling
unit
with
a
single-stage
thermostat
because
the
furnace
control
CPU
includes
a
programmed
adaptive
se-
quence
of
controlled
operation,
which
selects
low-
cooling
or
high-cooling
operation.
This selection
is
based
upon
the
stored
history
of
the
length
of
previous
cooling
period
of
the
single-stage
thermostat.
NOTE:
The
air
conditioning
relay
disable
jumper
ACRDJ
must
be
connected
to
enable
the
adaptive
cooling
mode
in
response
to
a
call
for
cooling.
(See
Fig.
26.)
When
ACRDJ
is
in
place
the
furnace
control
CPU
can
turn
on
the
air
conditioning
relay
ACR
to
energize
the
Y/Y2
terminal
and
switch
the
outdoor
unit
to
high-cooling.
The
furnace
control
CPU
can
start
up
the
cooling
unit
in
either
low-
or
high-cooling.
If
starting
up
in
low-cooling,
the
furnace
control
CPU
determines
the
low-cooling
on-time
(from
0
to
20
minutes)
which
is
permitted
before
switching
to
high-cooling.
If
the
power
is
interrupted,
the
stored
history
is
erased
and
the
furnace
control
CPU
will
select
low-cooling
for
up
to
20
minutes
and
then
energize
the
air
conditioning
relay
ACR
to
energize
the
Y/Y2
terminal
and
switch
the
outdoor
unit
to
high-cooling,
as
long
as
the
thermostat
continues
to
call
for
cooling.
Subsequent
selection
is
based
on
stored
history
of
the
thermostat
cycle
times.
The
wall
thermostat
“calls
for
cooling”,
closing
the
R-to-G-and-Y
circuits.
The
R-to-Y1
circuit
starts
the
outdoor
unit
on
low-cooling
speed,
and
the
R-to-G-and-Y1
circuits
starts
the
furnace
blower
motor
BLWM
at
low-cooling
airflow
which
is
the
true
on-board
CF
selection
as
shown
in
Fig.
57.
If
the
furnace
control
CPU
switches
from
low-cooling
to
high-cooling,
the
furnace
control
CPU
will
energize
the
air
conditioning
relay
ACR.
When
the
air
conditioning
relay
ACR
is
energized
the
R-to-Y1-and-Y2
circuits
switch
the
outdoor
unit
53
58CV

Related product manuals