21
Table 14 — 19XR Two-Stage Compressor Frame Sizes 6 and 7
Economizer Weight
*Includes economizer weight and all connecting piping to compressor.
Table 15 — Additional Weights for 19XR 150 psig (1034 kPa) Marine Waterboxes*
Two-Stage Compressors, Frame Size 6† — English (lb)
*Add to cooler and condenser weights for total weights. Cooler and
condenser weights may be found in Tables 10-13. The first digit of the
heat exchanger code (first column) is the heat exchanger frame size.
†Values are for Victaulic nozzles, two-pass dished head design.
Table 16 —Additional Weights for 19XR 150 psig (1034 kPa) Marine Waterboxes*
Two-Stage Compressors, Frame Size 6† — SI (kg)
*Add to cooler and condenser weights for total weights. Condenser
weights may be found in Tables 10-13. The first digit of the heat
exchanger code (first column) is the heat exchanger frame size.
†Values are for Victaulic nozzles, two-pass dished head design.
Table 17 — Additional Weights for 19XR 300 psig (2068 kPa) ASME Marine Waterboxes*
Two-Stage Compressors, Frame Size 6 — English (lb)
ASME — American Society of Mechanical Engineers
*Add to cooler and condenser weights for total weights. Cooler and
condenser weights may be found in Tables 10-13. The first digit of the
heat exchanger code (first column) is the heat exchanger frame size.
FRAME SIZE
DRY WEIGHT
(lb)*
REFRIGERANT
WEIGHT (lb)
OPERATION WEIGHT (lb)
DRY WEIGHT
(kg)*
REFRIGERANT
WEIGHT (kg)
OPERATION WEIGHT
(kg)
XR6 1589 360 1949 721 163 884
XR7 2749 646 3395 1247 293 1540
FRAME
NUMBER
OF
PASSES
COOLER CONDENSER
Rigging Wgt
Water Wgt
Rigging Wgt
Water Wgt
Victaulic Flange Victaulic Flange
A
1 2794 3124 6515 2582 2912 5648
2 2454 2650 2979 2236 2432 2613
3 2771 2899 4190 2840 3020 3950
B
1 — — — 2604 2934 6975
2 — — — 2459 2719 3600
3 — — — 2770 2950 4858
FRAME
NUMBER
OF
PASSES
COOLER CONDENSER
Rigging Wgt
Water Wgt
Rigging Wgt
Water Wgt
Victaulic Flange Victaulic Flange
A
1 1267 1417 2955 1171 1321 2562
2 1113 1202 2979 1014 1103 1185
3 1157 1315 1900 1288 1370 1792
B
1 — — — 1181 1331 3162
2 — — — 1115 1233 1633
3 — — — 1256 1338 2203
FRAME
NUMBER
OF
PASSES
COOLER CONDENSER
Rigging Wgt
Water Wgt
Rigging Wgt
Water Wgt
Victaulic Flange Victaulic Flange
A
1 6379 6709 5058 5573 5903 4426
2 5594 5790 2101 4834 5030 1890
3 6031 6159 3005 5310 5490 2688
B
1 — — — 7084 7414 5509
2 — — — 6474 6734 2577
3 — — — 6816 6996 3340