DETAI LED COOLING CAPACITIES# CONTINUED
EVAPORATOR AIR
CONDENSER ENTERING AIR TEMPERATURES ° F C)
75 (23.9) 85 (29.4) 95 (35) 105 (40.6) 115 (46.1) 125 (51.7)
CFM
EWB
°F(°C)
Capacity MBtuh
Tota l
Sys.
KW**
Capacity MBtuh
Tota l
Sys.
KW**
Capacity MBtuh
Tota l
Sys.
KW**
Capacity MBtuh
Tota l
Sys.
KW**
Capacity MBtuh
Tota l
Sys.
KW**
Capacity MBtuh
Tota l
Sys.
KW**
Tota l Sens‡ Tot a l Sens‡ To tal Sens‡ Tota l Sens‡ Tota l Sens‡ Tot al Sens‡
24ABB360A31 Outdoor Section With CAR**6034A** Indoor Section
1750
72 (22.2) 67.80 34.89 4.35 64.83 33.80 4.80 61.64 32.64 5.29 58.24 31.43 5.83 54.52 30.11 6.41 50.31 28.65 7.04
67 (19.4) 62.53 43.30 4.28 59.78 42.18 4.73 56.82 41.00 5.22 53.69 39.76 5.76 50.29 38.43 6.35 46.47 36.96 6.99
63 (17.2)†† 58.72 42.13 4.23 56.15 41.01 4.68 53.37 39.81 5.17 50.43 38.56 5.71 47.26 37.23 6.31 43.72 35.76 6.95
62 (16.7) 57.74 51.63 4.22 55.26 50.49 4.66 52.60 49.24 5.16 49.85 49.43 5.71 47.17 47.17 6.31 44.20 44.20 6.96
57 (13.9) 56.44 56.44 4.20 54.39 54.39 4.65 52.16 52.16 5.15 49.79 49.79 5.71 47.18 47.18 6.31 44.20 44.20 6.96
2000
72 (22.2) 68.70 36.53 4.46 65.64 35.43 4.91 62.33 34.26 5.40 58.81 33.03 5.94 54.97 31.69 6.52 50.63 30.21 7.14
67 (19.4) 63.42 45.98 4.39 60.56 44.86 4.83 57.50 43.66 5.33 54.27 42.41 5.87 50.76 41.06 6.46 46.84 39.55 7.09
63 (17.2)†† 59.63 44.67 4.34 56.94 43.52 4.78 54.07 42.32 5.28 51.04 41.05 5.82 47.76 39.69 6.41 44.11 38.17 7.06
62 (16.7) 58.86 55.26 4.33 56.34 55.78 4.78 53.88 53.88 5.28 51.35 51.35 5.83 48.55 48.55 6.42 45.37 45.37 7.07
57 (13.9) 58.44 58.44 4.32 56.26 56.26 4.78 53.88 53.88 5.28 51.35 51.35 5.83 48.56 48.56 6.42 45.38 45.38 7.07
2250
72 (22.2) 69.36 38.09 4.57 66.19 36.98 5.01 62.79 35.79 5.50 59.18 34.55 6.04 55.24 33.21 6.62 50.79 31.71 7.24
67 (19.4) 64.04 48.55 4.49 61.12 47.42 4.94 57.98 46.21 5.43 54.67 44.94 5.97 51.08 43.55 6.56 47.07 41.97 7.19
63 (17.2)†† 60.27 47.08 4.44 57.52 45.93 4.89 54.56 44.70 5.38 51.46 43.41 5.92 48.11 42.01 6.51 44.39 40.42 7.16
62 (16.7) 60.07 60.07 4.44 57.75 57.75 4.89 55.24 55.24 5.39 52.57 52.57 5.94 49.63 49.63 6.54 46.28 46.28 7.18
57 (13.9) 60.07 60.07 4.44 57.75 57.75 4.89 55.25 55.25 5.39 52.58 52.58 5.94 49.64 49.64 6.54 46.28 46.28 7.18
COOLING INDOOR
MODEL
CAPACITY POWER FURN ACE MODEL
*CAP**6024A** 1.00 1.00
CAP**6021A** 0.98 0.98
CNPH*6024A** 0.99 0.99
CNPV*6024A** 0.99 0.99
CSPH*6012A** 1.00 1.00
FV4BNB006 0.99 0.97
FX4CN(B,F)060 1.01 1.01
FY4ANB060 0.98 0.98
CAP**6021A** 0.97 0.97 58CV(A,X)110 ---20
CSPH*6012A** 0.98 0.98 58CV(A,X)110--- 20
CAP**6024A** 0.98 0.98 58CV(A,X)135 ---22
CNPH*6024A** 0.97 0.96 58CV(A,X)135--- 22
CNPV*6024A** 0.97 0.97 58CV(A,X)135--- 22
COOLING INDOOR
MODEL
CAPACITY POWER FURN ACE MODEL
CSPH*6012A** 0.98 0.97 58CV(A,X)135--- 22
CAP**6024A** 0.98 0.97 58CV(A,X)155 ---22
CNPH*6024A** 0.98 0.97 58CV(A,X)155--- 22
CNPV*6024A** 0.98 0.97 58CV(A,X)155--- 22
CSPH*6012A** 0.98 0.97 58CV(A,X)155--- 22
CAP**6021A** 0.98 0.98 58MEB100--- 20
CNPH*6024A** 0.98 0.98 58MEB100--- 20
CSPH*6012A** 0.98 0.98 58MEB100--- 20
CAP**6024A** 0.98 0.98 58MEB120--- 20
CNPH*6024A** 0.98 0.98 58MEB120--- 20
CNPV*6024A** 0.98 0.98 58MEB120--- 20
CSPH*6012A** 0.98 0.98 58MEB120--- 20
CAP**6021A** 0.97 1.01 58MV(B,C)080--- 20
COOLING INDOOR
MODEL
CAPACITY POWER FURN ACE MODEL
CAP**6021A** 0.97 0.99 58MV(B,C)100--- 20
CAP**6024A** 0.98 0.98 58MV(B,C)120--- 20
CAP**6021A** 0.97 0.97 58PH*090--- 16
CNPH*6024A** 0.97 0.97 58PH*090---16
CSPH*6012A** 0.97 0.97 58PH*090--- 16
CAP**6021A** 0.97 0.96 58PH*110--- 20
CNPH*6024A** 0.98 0.97 58PH*110---20
CSPH*6012A** 0.98 0.97 58PH*110--- 20
CAP**6024A** 0.97 0.97 58PH*135--- 20
CNPH*6024A** 0.97 0.97 58PH*135---20
CNPV*6024A** 0.97 0.97 58PH*135--- 20
CSPH*6012A** 0.97 0.97 58PH*135--- 20
* Tested combination.
{ Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
} Sensible capacities shown are based on 80_F(27_C) entering air at the indoor coil. For sensible capacities at other than 80_F(27_C), deduct 835 Btuh
(245 kW) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80_F(27_C), o r add 835 Btuh (245 kW) per 1000 C FM (480 L/S) of indoor coil air per degree above 80_F(27_C).
# Detailed cool ing capacities a re based on indoor and outdoor unit at th e same eleva tion per ARI standard 210/240 ---94. If additional tubing len gth and/or indoor unit is located above outdoor unit, a slight variation in capacity may
occur.
** System kw is total of i ndoor and outdoor unit kilowatts.
{{ At TVA rating indoor condition (75_F edb/63_F ewb). All other indoor air temperatures are at 80_F edb.
NOTE: When the required data falls between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.
EWB Entering Wet Bulb
NOTE: When the required data fall between the published data, interpolation may be performed. Extrapolation is not an acceptable practice.