7
ELECTRICAL DATA
UNIT
S I Z E ---
VOLTAGE,
SERIES
V/PH
OPER
VOLTS*
COMPR FAN
MCA
MIN WIRE
SIZE{
MIN WIRE
SIZE{
MAX
LENGTH
ft. (m)}
MAX
LENGTH
ft. (m)}
MAX
FUSE**
or CKT
BRK
AMPS
MAX MIN LRA RLA FLA 60° C 75° C 60° C 75° C
18---31
208/230/1 253 197
48.0 9.0 0.5 11.8 14 14 66 (20.1) 63 (21.0) 15
24---31 58.3 13.5 0.75 17.6 14 14 44 (13.4) 42 (12.8) 25
30---31 64.0 12.8 1.4 16.8 14 14 46 (14.0) 44 (13.4) 25
36---31 77.0 14.1 1.4 20.5 12 12 61 (18.6) 58 (17.7) 30
42---30 112.0 17.9 1.1 23.5 12 12 53 (16.2) 51 (15.5) 40
48---31 109.0 19.9 1.4 26.2 10 10 76 (23.2) 72 (22.2) 40
60---31 134.0 26.4 1.2 34.2 8 10 62 (18.9) 55 (16.8) 50
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C , consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of n on ---metallic---sh ea th ed cable (NM),
trade name ROMEX, shall be that of 60_C conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---pl a ted), 60 or 75_C
insulation, copper wire (solid wire for 10 AWG or smaller, stranded wi re for larger than 10 A WG) is used, consult applicable tables of the NEC (ANSI/NFPA
70).
} Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
* * T i m e --- D e l a y f u s e .
FLA --- Fu l l L o a d A m ps
LRA --- L oc k e d R o t o r Am ps
MCA --- Minimum Circuit Amps
RLA ---RatedLoadAmps
NOTE: Control circuit is 24--- V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
A--WEIGHTED SOUND POWER LEVEL
U N I T S I Z E ---
VOLTAGE,
SERIES
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125 250 500 1000 2000 4000 8000
18---31 72 53.5 59.5 63.5 67.0 63.5 59.0 52.5
24---31 76 55.0 61.5 67.0 71.5 69.0 61.0 55.0
30---31 74 55.0 63.5 68.5 68.5 65.5 61.0 54.0
36---31 75 59.5 63.0 68.5 70.0 65.5 61.5 53.5
42---30 78 57.5 65.0 71.0 73.0 70.5 67.5 62.5
48---31 80 58.5 67.5 73.5 75.0 70.5 67.5 64.5
60---31 78 59.0 67.5 71.5 73.5 69.0 66.0 63.5
NOTE: Tested in accordance with ARI Standard 270---95 (not listed in ARI).
A--WEIGHTED SOUND POWER LEVEL WITH SOUND SHIELD
U N I T S I Z E ---
VOLTAGE,
SERIES
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125 250 500 1000 2000 4000 8000
18---31 71 55.5 60.5 64.0 66.0 63.0 58.5 52.0
24---31 74 55.5 60.5 68.5 70.0 67.0 61.0 53.6
30---31 73 55.5 64.0 68.0 67.0 64.0 60.0 52.5
36---31 74 59.5 63.0 68.0 69.5 65.0 60.5 50.5
42---30 77 57.5 65.0 70.5 72.0 70.0 67.0 62.0
48---31 79 60.5 67.5 73.5 74.5 71.0 68.0 63.5
60---31 78 59.0 68.0 70.5 72.5 68.0 67.0 63.0
NOTE: Tested in accordance with ARI Standard 270---95 (not listed in ARI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE--- VOLTAGE & SERIES REQUIRED SUBCOOLING _F(_C)
18---31 10 (5.6)
24---31 10 (5.6)
30---31 10 (5.6)
36---31 14 (7.8)
42---30 10 (5.6)
48---31 15 (8.3)
60---31 13 (7.2)
24ABB3