FINAL CHECKS
IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring is routed away from tubing and
sheet metal edges to prevent rubthrough or wire
pinching.
2. Ensure that all wiring and tubing is secure in unit before
adding panels and covers. Securely fasten all panels and
covers.
3. Tighten service valve stem caps to 1/12turn past finger
tight.
4. Leave Users Manual with owner. Explain system
operation and periodic maintenance requirements outlined
in manual.
5. Fill out Dealer Installation Checklist and place in
customer file.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible
equipment failure, periodic maintenance must be performed on
this equipment.
Frequency of maintenance may vary depending upon geographic
areas, such as coastal applications. See Owners Manual for
information.
PURONR (R410A) REFRIGERANT QUICK REFERENCE GUIDE
Puron refrigerant operates at 5070 percent higher pressures than R22. Be sure that servicing equipment and replacement
components are designed to operate with Puron refrigerant.
Puron refrigerant cylinders are rose colored.
Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
Puron refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose
when charging into suction line with compressor operating.
Manifold sets should be 700 psig high side and 180 psig low side with 550 psig lowside retard.
Use hoses with 700 psig service pressure rating.
Leak detectors should be designed to detect HFC refrigerant.
Puron refrigerant, as with other HFCs, is only compatible with POE oils.
Vacuum pumps will not remove moisture from oil.
Do not use liquidline filter driers with rated working pressures less than 600 psig.
Do not leave Puron refrigerant suction line filter driers in line longer than 72 hours.
Do not install a suctionline filter drier in liquidline.
POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
POE oils may cause damage to certain plastics and roofing materials.
Wrap all filter driers and service valves with wet cloth when brazing.
A factoryapproved liquidline filter drier is required on every unit.
Do NOT use an R22 TXV.
If indoor unit is equipped with an R22 TXV or piston metering device, it must be changed to a hardshutoff Puron refrigerant TXV.
Never open system to atmosphere while it is under a vacuum.
When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers.
Evacuate to 500 microns prior to recharging.
Do not vent Puron refrigerant into the atmosphere.
Do not use capillary tube coils.
Observe all warnings, cautions, and bold text.
All indoor coils must be installed with a hardshutoff Puron refrigerant TXV metering device.
Copyright 2006 Carrier Corp. 7310 W. Morris St. Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: 25HNA3SI
Replaces:25HNA2SI
Printed in U.S.A. Edition Date:09/06