Table 2—Accessory Usage
ACCESSORY
REQUIRED FOR
LOW−AMBIENT APPLICATIONS
(Below 55 5F)
REQUIRED FOR LONG LINE
APPLICATIONS*
(Over 80 ft.)
REQUIRED FOR SEA
COAST APPLICATIONS
(Within 2 miles)
Crankcase Heater Standard Standard Standard
Evaporator Freeze Protection
Standard with Infinity Control
(Low Ambient not allowed with non−
communicating thermostat)
No
No
Winter Start Control
Standard with Infinity Control
(Low Ambient not allowed with non−
communicating thermostat)
No
No
Compressor Start Assist Capacitor
and Relay}
Standard on 25HNA6 models.
Not required on 25HNA9 models
since compressor always starts
unloaded.
Standard on 25HNA6 models.
Not required on 25HNA9 models
since compressor always starts
unloaded.
Standard on 25HNA6
models.
Not required on 25HNA9
models since compressor
always starts unloaded.
Low−Ambient Control
Standard with Infinity Control (Low
ambient not allowed with non−commu-
nicating thermostat)
No
No
Support Feet Recommended
No
Recommended
Liquid−Line Solenoid Valve No Yes No
Ball−Bearing Fan Motor Standard
Standard
Standard
Puron Refrigerant Balance Port
Hard−ShutOff TXV
Yes Yes Yes
* For tubing set lengths between 80 and 200 ft. horizontal or 20 ft. vertical differential (total equivalent length), refer to the Long Line GuidelineAir Conditioners
and Heat Pumps using Puron Refrigerant.
Required on all indoor units. Standard on all new Puron refrigerant fan coils and furnace coils.
Information is specific to 25HNA6 and 25HNA9 models.
Install LiquidLine Filter Drier Indoor
Refer to Fig. 5 and install filter drier as follows:
1. Braze 5in. liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5in. liquid tube. Flow arrow must
point towards indoor coil.
4. Connect and braze liquid refrigerant tube to the filter drier.
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage
or improper operation.
Installation of filter drier in liquid line is required.
A05227
Fig. 5LiquidLine Filter Drier
Refrigerant Tubing connection Outdoor
Connect vapor tube to fitting on outdoor unit vapor service
valves (see Table 1).
Install Adapter Tube
1. Remove plastic retainer holding outdoor piston in liquid
service valve.
2. Check outdoor piston size with matching number listed on
unit rating plate.
3. Locate plastic bag taped to unit containing adapter tube.
4. Remove Teflon washer from bag and install on open
end of liquid service valve.
5. Remove adapter tube from bag and connect threaded nut
to liquid service valve. Tighten nut finger tight and then
with wrench tighten an additional 1/2 turn (15 ftlb).
DO NOT OVERTIGHTEN!
Sweat Connections
CAUTION
!
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage or improper operation.
Service valves must be wrapped in a heatsink
material such as a wet cloth.
Use refrigerant grade tubing. Service valves are closed from
factory and ready for brazing. After wrapping service valve with
a wet cloth, braze sweat connections using industry accepted
methods and materials. Consult local code requirements.
Refrigerant tubing and indoor coil are now ready for leak testing.
This check should include all field and factory joints.
25HNA