10
224.84
8.85[]
PIPING ENTRANCE AREA
2446.09
96.30[]
916.15
36.07[]
z
PD
z
PS
761.94
30.00[]
2236.08
88.03[]
CG
x
y
CG
2281.37
89.82[]
3587.08
141.22[]
408.89
16.10[]
408.89
16.10[]
PD
x
515.82
20.31[]
PS
x
2728.56
107.42[]
391.88
15.43[]
PS
y
PD
y
860.81
33.89[]
246.36
9.70[]
336.50
13.25[]
190.00
7.48[]
200.00
7.87[]
45.00
1.77[]
100.00
3.94[]
RIGGING HOLE
38.00
1.50[]
UNIT MOUNTING2769.30
109.03[]
1447.8[57.0]
UNIT MOUNTING
2156.30
84.89[]
992.44
39.07[]
2438.40
[96.00]
938.35
36.94[]
39.89
1.57[]
215.73
8.49[]
WEIGHT
CU/AL
lb/kg
MAX WEIGHT
CU/AL PUMP
lb/kg
WEIGHT
CU/CU
lb/kg
MAX WEIGHT
CU/CU PUMP
lb/kg
WEIGHT
MCHX
lb/kg
MAX WEIGHT
MCHX PUMP
lb/kg
CENTER OF GRAVITY PUMP SUCTION (PS) PUMP DISCHARGE (PD)
CGx
MM [INCH]
CGy
MM [INCH]
X
.25
Y
.25
Z
.25
X
.25
Y
.25
Z
.25
30RB-110
6519
2963
7442
3383
7243
3292
8166
3712
6027
2734
6950
3152
1713
[67.44]
997
[39.25]
856.0
[33.7]
281.9
[11.1]
60.9
[2.4]
340.4
[13.4]
391.2
[15.4]
233.7
[9.2]
CIRCUIT A
COMPRESSORS
CIRCUIT B
COMPRESSORS
FAN ELECTRICAL BOX
(230V ONLY)
(FEB)
AIR FLOW
COIL SERVICE AREA
COIL SERVICE AREA
COOLER VENT
1/4" NTP
COOLER DRAIN
3/4" NPT
PUMP PACKAGE
LEAVING WATER
6" VICTAULIC
NO PUMP PACKAGE
ENTERING WATER
6" VICTAULIC
(SEE NOTE 4)
SEE DETAIL
B
PUMP PACKAGE ENTERING WATER
6" VICTAULIC
COOLER TUBE
SERVICE AREA
SERVICE AREA 1219.2[48.0] FROM EACH SIDE OF THE UNIT
DETAIL B
SCALE 3:16
22.2[.87]
MOUNTING HOLE
POWER BOX 230V
CONTROL/POWER BOX
380V,460V,575V
7/8" KNOCKOUT TO BE
USED FOR LOCATING
FIELD POWER WIRING
SCROLLING MARQUEE
DISPLAY
BACnet COMMUNICATION
OPTION KNOCKOUT
FOR 1/2" CONDUIT
FIELD CONTROL WIRING
NOTES:
1. Unit must have clearances as follows:
Top — Do not restrict.
Sides and End — 6 (1.8 m) from solid surface.
Airflow Side — 8 (2.4 m) required for coil service
area.
2. All pumps have drains located at the bottom of
volute for draining.
3. Temperature relief devices ocated on suction line,
liquid line and filter drier of each circuit and have
1
/
4
flare connection.
4. No pump package leaving water connection is
same size and has same Y and Z dimensions as
entering water. Also has same PDx dimension as
pump package.
5. Dimensions are in mm [inches].
a30 5332
MCHX — Microchannel Condenser Coil
Fig. 6 — 30RB110 Air-Cooled Chiller Dimensions