180 200 220 300 330 400 430 470 520
Nominal voltage
V-ph-Hz 400 - 3 -50
Voltage range
V 360 - 440
24 V via internal transformer
Circuit A&B
A 100 110 124 133 161 180 201 221 242 261 282 322
(2)
Circuit A&B
kW 80 88 99 107 129 145 161 177 194 210 226 258
(2)
0,88 0,87 0,87 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88
(3)
Circuit A&B
A 144 158 176 192 230 259 288 317 345 374 403 460
Circuit A&B - Standard unit
A 133 146 163 177 212 239 266 292 319 345 372 425
Circuit A&B - Unit + option 231
A 100 110 125 133 163 181 204 222 244 262 285 326
(5)
Circuit A&B
A 307 356 374 352 423 450 476 503 529 556 583 636
(5)
Circuit A&B
A 261 283 300 305 349 376 403 429 456 482 509 562
(1) Conditions equivalent to the standardised Eurovent conditions (water type heat exchanger water input/output temperature = 12°C/7°C, outdoor air temperature = 35°C).
(2) Power input, compressors and fans, at the unit operating limits (saturated intake temperature 15°C, saturated condensation temperature 68.3°C) and nominal voltage of 400 V (data given on the unit
name plate).
(3) Maximum unit operating current at maximum unit power input and 360 V.
(4) Maximum unit operating current at maximum unit power input and 400 V (values given on the unit name plate).
(5) Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor).
Fan motor electrical data: at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: 3.8 A, start-up current 20 A, power input 1.75 kW.
180 200 220 300 330 400 430 470 520
Nominal voltage V-ph-Hz 400 - 3 -50
Voltage range V 360 - 440
24 V via internal transformer
(1)
Circuit A&B A 97 107 121 130 158 176 197 216 237 255 276 316
(2)
Circuit A&B kW 81 88 99 108 129 145 162 178 194 210 226 259
(2)
0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88 0,88
(3)
Circuit A&B A 142 154 173 189 227 255 284 312 340 369 397 454
(4)
Circuit A&B - Standard unit A 131 142 160 174 209 235 262 287 314 340 366 419
Circuit A&B - Unit + option 231 A 98 108 123 131 161 178 201 219 241 259 281 321
(5)
Circuit A&B A 305 353 371 349 420 446 472 498 525 550 577 629
(5)
Circuit A&B A 259 279 297 302 346 372 399 424 451 477 503 556
(1) Conditions equivalent to the standardised Eurovent conditions (water type heat exchanger water input/output temperature = 12°C/7°C, outdoor air temperature = 35°C).
(2) Power input, compressors and fans, at the unit operating limits (saturated intake temperature 15°C, saturated condensation temperature 68.3°C) and nominal voltage of 400 V (data given on the unit
name plate).
(3) Maximum unit operating current at maximum unit power input and 360 V.
(4) Maximum unit operating current at maximum unit power input and 400 V (values given on the unit name plate).
(5) Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + fan current + locked rotor current of the largest compressor).
Fan motor electrical data reported upstream of the variable speed drive at Eurovent equivalent conditions and motor ambient air temperature of 50°C at 400 V: current 3.0 A; starting current 20 A; power
input: 1.75 kW.
Short circuit stability current (TN system
(1)
)
180 200 220 300 330 400 430 470 520
Circuits A&B kA/kA 8/30 8/30 8/30 8/30 8/30 8/30 8/30 15/65 15/65 15/65 15/65 20/80
Circuits A & B A 200 200 200 200 250 250 250 315 400 400 400 630
Circuits A & B kA 50 50 50 50 50 50 50 50 50 50 50 50
(1) Type of system earthing
IT system: the short-circuit holding current values given above for the TN system are not valid for IT; modications are
required.