12.2.6 - Brine option (Options 5B and 6B)
The 5B medium-temperature brine solution option is used to
produce low temperature chilled water down to 0°C.
Production of brine solution from 0°C to -15°C is only possible
with the 6B low-temperature brine solution.
The unit is equipped with insulation on the intake tubes. The
insulation is reinforced on the low-temperature brine solution
option.
The operating range depends on:
the size of the unit,
the glycol type,
its concentration,
the ow rate,
the temperature of the glycol solution,
the condensation pressure (ambient temperature).
Operating range
Low-temperature brine solution


-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6
Opons 28B-28C pour taille RBM 160
Opons 28B-28C pour RBM
RBP
48
31
Brine solution mix type heat exchanger leaving water temperature (°C)
Medium-temperature brine solution


-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-2 -1 0 1 2 3 4 5 6
Opons 28B-28C pour taille RBM 160
Opons 28B-28C pour RBM
RBP ou Opon 28 pour RBM
43
48
Brine solution mix type heat exchanger leaving water temperature (°C)


-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
-20 -19 -18 -17 -16 -15 -14 -13 -12 -11 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 1 2 3 4 5 6 7
Options 28B-28C pour taille RBM 160
RBM Options 28B-28C
RBP
28
48
Inlet air temperature (°C)
Brine solution type heat exchanger leaving water temperature (°C)

- Evaporator ∆T = 5K max
- These operating ranges are guidelines only. Verify the operating range with the
Carrier electronic catalogue.

Operating range for 30RBM or 30RBP brine solution unit
Operating range for 30RBM unit equipped with options 28B and 28C (winter
operation). Options 28B-28C (with two-speed lead fan for each circuit) allows
operation down to -10 °C outside temperature.
RBP operating range or extension of the operating range, 30RBM unit
equipped with option 28. Option 28 (with variable-speed lead fan for each
circuit) allows operation down to -20°C outside temperature.
Inlet air temperature (°C)Inlet air temperature (°C)
Options 28B-28C for RBM
Options 28B-28C for size RBM 160
RBP
RBM Options 28B-28C
Options 28B-28C for size RBM 160
RBP
Options 28B-28C for RBM
Options 28B-28C for size RBM 160
RBP or Option 28 for RBM

Table of Contents