: period 1 0h00 3h00 Monday
: period 2 7h00 18h00 Monday and Tuesday
: period 3 7h00 21h00 Wednesday
: period 4 7h00 17h00 Thursday and Friday
: period 5 7h00 12h00 Saturday
: period 6 20h00 21h00 Public holidays
: period 7 Not used in this example
: period 8 Not used in this example
Occupied
Unoccupied
MON: Monday
TUE: Tuesday
WED: Wednesday
THU: Thursday
FRI: Friday
SAT: Saturday
SUN: Sunday
HOL: Public holidays
ATTENTION: The broadcast function must be activated
to utilise the holiday schedule, even if the unit is running
in stand-alone mode (not connected to CCN). See section
4.3.11.8.
0 HoLidAy X Sub-menu When selected this item authorises a return to
the conguration menu.
1 0 to 12
0 = period not in use
1 = January, 2 = February, etc.
2 0 to 31 . 0 period
not in use.
3 0 to 99 days .
:
A public holiday period lasting 1 day on 20th May, for instance, is congured as
follows: start month = 5, start day = 20, duration = 1
A public holiday period lasting 2 day on 25th May, for instance, is congured as
follows: start month = 5, start day = 25, duration = 2
4.3.11.8 - Description of the Broadcast sub-menu
(broAdCASt)
The controller provides a broadcast configuration menu
which you can use to configure the unit to be the CCN’s
broadcaster, responsible for transmitting the time, outdoor
temperature, and holiday flags to all system elements.
This menu also authorises setting the date of the daylight
saving time. There should be only one broadcaster in a
CCN, so this table should not be configured if any other
system element is acting as broadcaster.
ATTENTION: If the unit operates in standalone mode
(not CCN connected) this menu can also must be used if
the holiday function is used or to correct for daylight
saving time.
Typical timer program:
4.3.11.7 - Description of the Holidays sub-menus
This function is used to define 16 public holiday periods.
Each period is defined with the aid of three parameters:
the month, starting day and duration of the public holiday
period. During these public holidays the controller will be
in occupied or unoccupied mode, depending on the
programmed periods validated for public holidays.
Each of these public holiday periods can be displayed and
changed with the aid of a sub-menu.
0 broAdCASt MEnu When selected this item authorises a return to the main menu.
1 YES/no Determines whether or not the unit is a when the unit is connected on a CCN network. There must be only
in a CCN.
: if the unit operates in standalone mode (not CCN connected) this choice must be set to Yes if the holiday function is used (see
section 4.3.11.6) or if you want to congure the daylight saving time function.
2 0/1/2 This item permits .
0 = the controller is not the broadcaster, and it is not useful to congure another selection in this table.
1 = broadcasts time, date, holidays and the outside temperature.
2 = for chillers only. Summertime and holidays are not taken into consideration without broadcasting the information on the bus.
3 nnn : it is the bus number of the system that has the outside air temperature sensor connected to it.
4 nnn : it is the element number of the system element that has the outside air temperature sensor connected
to it.