15
6.2 - Detailed menu description
Icon Displayed text* Description Associated table
General Parameters General parameters GENUNIT
Temperatures Temperatures TEMP
Pressures Pressures PRESSURE
Inputs Status Inputs status INPUTS
Outputs Status Outputs status OUTPUTS
Pump Status Pump status PUMPSTAT
Run Times Run times RUNTIME
Modes Modes MODES
Reclaim Reclaim RECLAIM
Freecooling Free cooling FREECOOL
Setpoint Table Setpoint table SETPOINT
Trendings Trendings TRENDING
Conguration Menu Conguration menu CONFIG
* Depends on the selected language (English by default).
GENUNIT – General parameters
No. Status Unit
Displayed text* Description
1 0 to 3 - Local=0 Net.=1 Remote=2 Operating mode:
0 = Local
1 = Network
2 = Remote
2 - - Run Status Unit running status: O, Stopping, Delay,
Running, Ready, Override, Tripout, Test, Runtest
3 0 to 1 - Net.: Cmd Start/Stop Unit start/stop via Network
4 0 to 1 - Net.: Cmd Occupied Unit time schedule via Network
5 - min Minutes Left for Start Minutes before the unit start-up
6 - - Heat/Cool status Heating/cooling status
7 0 to 2 - Heat/Cool Select Heating/cooling selection
8 - - 0=Cool. 1=Heat. 2=Auto 0 = Cooling
1 = Heating
2 = Automatic heating/cooling control
9 0 to 2 - Setpoint Select Setpoint selection
10 - - 0=Auto. 1=Spt1. 2=Spt2 0 = Automatic setpoint selection
1 = Setpoint 1
2 = Setpoint 2
11 0 to 1 - Setpoint Occupied? Setpoint status
12 0 to 100 % Percent Total Capacity Total unit capacity
13 - A Actual Chiller Current Actual chiller current
14 0 to 200 A Chiller Current Limit Chiller current limit
15 - °C Current Setpoint Current setpoint value
16 - - Control Point Control point
17 0 to 1 - Emergency Stop Emergency stop
18 0 to 100 % Active Demand Limit Val Active demand limit value
* Depends on the selected language (English by default)