22
No. Status Default Unit Displayed text* Description
1 0 to 4 0 - Condenser Pumps Sequence Condenser pumps sequence **
2 0 to 4 0 - Cooler Pumps Sequence Evaporator pumps sequence
3 0 = No Pump 0 = No pump
4 1 = One Pump Only 1 = One pump
5 2 = Two Pumps Auto 2 = Two pumps automatic control
6 3 = Pump#1 Manual 3 = Pump 1 manual
7 4 = Pump#2 Manual 4 = Pump 2 manual
8 24 to 3000 48 hour Pump Auto Rotation Delay Pump rotation delay
9 no/yes no - Pump Sticking Protection Pump sticking protection
10 no/yes no - Stop Pump During Standby Pump stop when the unit is in standby
11 no/yes yes - Flow Checked If Pump O Flow check when the pump is o
12 no/yes no - Cooler Pump O In Heat Evaporator pump o in Heating
13 no/yes no - Cond Pump O In Cool Condenser pump o in Cooling
*Depends on the selected language (English by default).
** Please note that the unit can control only one condenser pump. This value can be set to “0” or “1”.
No. Status Default Unit Displayed text* Description
1 1 to 9999 11 - User Password User password
*Depends on the selected language (English by default).
No. Status Default Unit Displayed text* Description
1 0 to 4 0 - Cooling Reset Select Cooling reset selection
2 0 to 4 0 - Heating Reset Select Heating reset selection
3 0=None, 1=OAT 0 = None
1 = OAT
4 2=Delta T, 4=Space Temp 2 = Delta T
4 = Space temperature
5 3=4-20mA control 3 = 4-20 mA control
6 Cooling Cooling
7 -10 to 51.7 -10 °C OAT No Reset Value OAT, no reset value
8 -10 to 51.7 -10 °C OAT Full Reset Value OAT, max. reset value
9 0 to 13.9 0 ^C Delta T No Reset Value Delta T, no reset value
10 0 to 13.9 0 ^C Delta T Full Reset Value Delta T, max. reset value
11 0 to 20 0 mA Current No Reset Value Current, no reset value
12 0 to 20 0 mA Current Full Reset Value Current, max. reset value
13 -10 to 51.7 -10 °C Space T No Reset Value Space temperature, no reset value
14 -10 to 51.7 -10 °C Space T Full Reset Value Space temperature, max. reset value
15 -16.7 to 16.7 0 ^C Cooling Reset Deg. Value Maximum cooling reset value
16 Heating Heating
17 -10 to 51.7 -10 °C OAT No Reset Value OAT, no reset value
18 -10 to 51.7 -10 °C OAT Full Reset Value OAT, max. reset value
19 0 to 13.9 0 ^C Delta T No Reset Value Delta T, no reset value
20 0 to 13.9 0 ^C Delta T Full Reset Value Delta T, max. reset value
21 0 to 20 0 mA Current No Reset Value Current, no reset value
22 0 to 20 0 mA Current Full Reset Value
Current, max. reset value
23 -10 to 51.7 -10 °C Space T No Reset Value Space temperature, no reset value
24 -10 to 51.7 -10 °C Space T Full Reset Value Space temperature, max. reset value
25 -16.7 to 16.7 0 ^C Heating Reset Deg. Value Maximum heating reset value
26 -4 to 32 -17.8 °C Heating OAT threshold Heating OAT threshold
27 no/yes no - HSM Both Command Select HSM both command selection
28 no/yes no - Auto Changeover Select Automatic changeover selection
*Depends on the selected language (English by default).
No. Name Displayed text* Description
1 OCCPC01S OCCPC01S - Schedule Menu Unit on/o time schedule
2 OCCPC02S OCCPC02S - Schedule Menu Unit setpoint selection time schedule
*Depends on the selected language (English by default).