ELECTRICAL DATA
Table 13 — Electrical Data
*Permissible limits of the voltage range at which the unit will operate satisfactorily.
LEGEND
FLA - Full Load Amps
MCA - Minimum Circuit Amps
MOP- Maximum Overcurrent Protection
OUTDOOR UNIT
12K 115V 09K 12K 18K 24K 30K 36K
(115V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V) (208/230V)
MINIMUM CIRCUIT AMPACITY (MCA) A18121218242833
MOP A20151520253035
VOLTAGE-PHASE-FREQUENCY 115-1-60 208/230-1-60
MAX – MIN VOLTAGE RANGE* 127-104 253-187
COOLING
RUNNING CURRENT (A) 10.3 4.7 4.1 6.3 7.4 11.2 18
POWER CONSUMPTION (W) 923 604 916 1406 1714 2500 4138
HEATING
RUNNING CURRENT RANGE (A) 10.5 3.3 4 6.7 8.3 13.1 16.2
POWER CONSUMPTION (W) 950 750 902 1507 1852 2857 3700