Fig. 1 — Sizes 06K-36K
NOTES: Read the entire instruction manual before starting the
installation. Images are for illustration purposes only.
Actual models may differ slightly.
TABLE OF CONTENTS
PAGE
SAFETY CONSIDERATIONS........................................................2
ACCESSORIES................................................................................7
MODEL NUMBERS........................................................................8
CAPACITY ......................................................................................8
DIMENSIONS..................................................................................9
ELECTRICAL DATA......................................................................10
INSTALLATION OVERVIEW.......................................................10
INSTALLATION SUMMARY........................................................11
INDOOR UNIT INSTALLATION ..................................................14
Step 1: Select Installation Location ..................................................14
Step 2: Drill Wall Hole for Connecting Piping ................................15
Step 3: Install Refrigerant Pipe & Drain Hose .................................16
Step 4: Electrical Work Preparation .................................................19
Step 5: Wrap Piping and Cables .......................................................20
Step 6: Mount the Indoor Unit..........................................................21
WIRELESS REMOTE CONTROLLER INSTALLATION............23
OPTIONAL WIRED WALL-MOUNTED REMOTE CONTROL IN-
STALLATION .................................................................................23
TROUBLESHOOTING ...................................................................24
DUCTLESS START-UP CHECKLIST - Single Zone ....................27
Installation Instructions
45MAHAQ
High Wall Unit Ductless System
Sizes 06K-36K
Question and Answer IconNeed help?

Do you have a question about the Carrier 37MAHAQ33AA3 and is the answer not in the manual?

Overview

The 45MAHAQ High Wall Unit Ductless System is a sophisticated air-conditioning unit designed for residential and light commercial applications. It offers efficient cooling and heating, with models ranging from 06K to 36K in capacity. The system is designed for ease of installation and maintenance, while adhering to strict safety and performance standards.

Function Description

The 45MAHAQ system operates as a high wall unit, providing conditioned air to an indoor space. It's a ductless system, meaning it does not require extensive ductwork, making it suitable for installations where traditional ducted systems are impractical or undesirable. The system consists of an indoor unit (45MAHAQ series) and an outdoor unit (37MAHAQ or 37MARAQ series), which work in conjunction to regulate indoor temperature.

Key functions include:

  • Cooling and Heating: The primary function is to provide both cooling and heating, ensuring year-round comfort.
  • Air Circulation: The indoor unit features a louver and air filter to circulate and clean the air.
  • Remote Control: The system can be operated via a wireless remote controller (RG10L5) or an optional wired wall-mounted remote control, offering convenience and precise temperature management.
  • Refrigerant Leak Detection: Some models are equipped with a refrigerant sensor that detects leaks, displaying an error code (ECC1, EHC1, EHC2, EHC3, FHCC) and emitting a buzzing sound. In case of a leak, the outdoor unit compressor stops, and the indoor fan continues running.
  • Overcurrent Protection: The air conditioner's circuit board (PCB) includes a fuse for overcurrent protection, with specifications (e.g., T3.15AL/250VAC, T5AL/250VAC) printed on the board. Only blast-proof ceramic fuses should be used.
  • Self-Protection Features: The unit incorporates a 3-minute protection feature to prevent overloading, delaying restart for three minutes after being turned off. It also adjusts settings to prevent frost formation in heating mode.

Important Technical Specifications

The 45MAHAQ system comes in various capacities, with corresponding indoor and outdoor unit model numbers.

Capacities and Model Numbers:

  • 06K: 6,000 BTUh (Indoor: 45MAHAQ06XA3, Outdoor: 37MAHAQ06AA3)
  • 09K: 9,000 BTUh (Indoor: 45MAHAQ09XA3, Outdoor: 37MAHAQ09AA3 or 37MARAQ09AA3)
  • 12K: 12,000 BTUh (Indoor: 45MAHAQ12XA1 for 115V, 45MAHAQ12XA3 for 208/230V; Outdoor: 37MARAQ12AA1 for 115V, 37MARAQ12AA3 or 37MAHAQ12AA3 for 208/230V)
  • 18K: 18,000 BTUh (Indoor: 45MAHAQ18XA3, Outdoor: 37MAHAQ18AA3 or 37MARAQ18AA3)
  • 24K: 24,000 BTUh (Indoor: 45MAHAQ24XA3, Outdoor: 37MAHAQ24AA3 or 37MARAQ24AA3)
  • 30K: 30,000 BTUh (Indoor: 45MAHAQ30XA3, Outdoor: 37MAHAQ30AA3 or 37MARAQ30AA3)
  • 33K: 33,000 BTUh (Indoor: 45MAHAQ33XA3, Outdoor: 37MAHAQ33AA3 or 37MARAQ33AA3)
  • 36K: 36,000 BTUh (Indoor: 45MAHAQ36XA3, Outdoor: 37MAHAQ36AA3 or 37MARAQ36AA3)

Electrical Data (208/230V models):

  • Minimum Circuit Ampacity (MCA): 3A for all models.
  • Maximum Overcurrent Protection (MOP): 15A for all models.
  • Voltage-Phase-Frequency: 208/230-1-60.
  • Max - Min Voltage Range: 253-187V.

Electrical Data (115V models - 12K only):

  • Minimum Circuit Ampacity (MCA): 3A.
  • Maximum Overcurrent Protection (MOP): 15A.
  • Voltage-Phase-Frequency: 115-1-60.
  • Max - Min Voltage Range: 127-104V.

Dimensions (Indoor Unit, Net):

  • 06K, 09K, 12K (115V/208-230V): Height: 11.61 in (295 mm), Width: 31.30 in (795 mm), Depth: 8.86 in (225 mm).
  • 18K: Height: 12.56 in (319 mm), Width: 37.99 in (965 mm), Depth: 9.41 in (239 mm).
  • 24K, 30K, 33K, 36K: Height: 14.57 in (370 mm), Width: 44.88 in (1140 mm), Depth: 10.83 in (275 mm).

Refrigerant Piping:

  • Liquid Side: Φ1/4 in (Φ6.35mm) for 06K, 09K, 12K, 18K; Φ3/8 in (Φ9.52mm) for 24K, 30K, 33K, 36K.
  • Gas Side: Φ3/8 in (Φ9.52mm) for 06K, 09K, 12K; Φ1/2 in (Φ12.7mm) for 18K; Φ5/8 in (Φ16mm) for 24K, 30K, 36K; Φ3/4 in (Φ19mm) for 33K.
  • Flare Nut Spacing: Specific dimensions (MAX/MIN) for different pipe diameters to ensure proper connection.
  • Tightening Torque: Recommended seating torque for brass flare nuts, ranging from 8-10 Ft.-Lbs. (10.8-13.6 N-m) for Ø1/4 to 50-55 Ft.-Lbs. (68.0-74.6 N-m) for Ø3/4.

Airflow Information (Nominal Air Volume CFM (M³/H)):

  • 09K: 353 (600)
  • 12K: 418 (710)
  • 18K: 448 (760)
  • 24K: 765 (1300)
  • 36K: 1042 (1770)
  • 48K: 1236 (2100)

Flammable Refrigerant (R-454B, Safety Group A2L):

  • The appliance uses a flammable refrigerant. Special precautions are required during installation and servicing to prevent fire risk.
  • Minimum room area requirements are specified in Table 1-A (min) based on refrigerant charge and indoor unit height. The indoor unit should be installed at least 6.0ft/1.8m from the floor, and the room height should not be less than 7.3ft/2.2m.

Usage Features

  • Installation Location: Requires good air circulation, convenient drainage, a firm and solid location that won't vibrate and can support the unit's weight. It should be at least 3.2 ft/1m from other electrical devices and away from heat sources, flammable items, doorways, or direct sunlight.
  • Piping and Wiring: The system allows for piping to exit from both the left and right sides of the indoor unit. Proper routing of refrigerant pipes, drain hose, and electrical cables is crucial for performance and safety.
  • Drain Hose: Must be installed at the bottom of the bundle to prevent water damage and overflow.
  • Remote Control: The wireless remote controller allows users to adjust mode, temperature, fan speed, and other settings. The wired wall-mounted remote control offers similar functionality with a fixed installation.
  • Kickstand: The indoor unit is equipped with a kickstand to provide more room for connecting refrigerant piping, signal cable, and the drain hose during installation.
  • Maintenance Access: The design allows for easy access to the top air filter for cleaning, requiring a minimum distance from the ceiling (3.93in/10cm or more if no kickstand, 8.67in/22cm or more if kickstand is used with front panel open, 4.33in/11cm or more if kickstand is used without front panel).

Maintenance Features

  • Air Filter Cleaning: The air filter (Part 4 in Fig. 3) can be pulled upwards for cleaning. Regular cleaning is recommended to maintain air quality and unit performance.
  • Troubleshooting: The manual provides a comprehensive troubleshooting guide (Table 11 - Error Codes, Table 12 - Refrigerant Leak Detection Error Codes, Table 13 - Common Issues, Table 14 - Common Issues) to help diagnose and resolve common problems. Error codes displayed on the indoor unit's window (e.g., E(x), P(x), F(x), EH(xx), EL(xx), EC(xx), PH(xx), PL(xx), PC(xx)) indicate specific malfunctions.
  • Refrigerant Sensor Replacement: If the refrigerant sensor malfunctions (FHCC error code), it cannot be repaired and must be replaced by the manufacturer's specified sensor.
  • Leak Testing: After installation, field-made refrigerant joints must be tightness tested with detection equipment sensitive to 1/8 oz (5g)/year of refrigerant or better.
  • Evacuation and Charging: Specific procedures for evacuation and charging with oxygen-free nitrogen are outlined, emphasizing safety for flammable refrigerants. Charging must be performed by the liquid charging method, and the system must be grounded.
  • Professional Servicing: Installation, modification, and servicing should only be performed by trained, qualified installers and service mechanics due to system pressures, electrical components, and equipment location hazards. Untrained personnel can perform basic maintenance like coil cleaning.
  • Parts and Accessories: Only manufacturer-approved accessories and replacement parts should be used to ensure continued performance, reliability, and safety.
  • Wiring Inspection: Regular checks of cabling for wear, corrosion, excessive pressure, vibration, sharp edges, or other adverse environmental effects are recommended.
  • Start-up Checklist: A detailed "Ductless Start-Up Checklist - Single Zone" is provided, covering installation data, wiring electrical checks, voltage checks, piping leak checks, evacuation methods, and performance checks.