Table
2
Refrigerant
Piping
Sizes
SINGLE
SUCTION
RISERS
LENGTH
OF
INTERCONNECTING
PIPING
(F
L-Liquid
Line
S-Suction
Line
*
IMPORTANT
Requires
a
double
suction
riser,
see
below:
NOTE:
Liquid
and
suction
line
sizes
are
OD
(in)
CONDENSING
UNIT
AX
(914
mm)
MAXIMUM
LIQUID
LIFT
UNIT
38AK
EVAPORATOR
(A)
-
SUCTION
RISER
WITHOUT
TRAP
-
SUCTION
RISER
WITH
TRAP
(C)
-
SUCTION
LINE
TO
CONDENSING
UNIT
DOUBLE
SUCTION
RISERS
LENGTH
OF
INTERCONNECTING
PIPING
(F
101-200
NOTE:
A,
B,
C
dimensions
relate
to
reference
diagram
SUCTION
PIPING
ATEVAPORATOR
AND
TXV
BULB
LOCATION
(See
Fig.
5)
The
purpose
of
these
recommendations
is
to
achieve
good
mixing
of
the
refrigerant
leaving
the
evaporator
suction
header
for
proper
sensing
by
the
TXV
bulb.
l.
A
minimum
of
two
90?
elbows
must
be
installed
Suction
piping
for
the
high
velocity
section
should
be
selected
for
about
0.5
degree
F
friction
loss.
If
a
2
degree
F
loss
is
allowed
for
the
entire
suction
line,
1.5
degree
F
is
left
for
the
balance
of
the
suction
line
and
it
should
be
sized
on
that
basis.
Check
that
the
high-velocity
sizing
is
adequate
for
oil
return
up
the
riser.
2.
upstream
of
the
expansion
valve
bulb
location.
The
TXV
sensing
bulb
should
be
located
on
a
vertical
riser
where
possible.
If
a
horizontal
location
is
neces-
sary,
secure
the
bulb
at
approximately
the
4
o'clock
If
an
oil
return
connection
at
the
bottom
of
this
suction
header
is
supplied
with
an
evaporator,
this
connection
must
be
teed-in
ahead
of
first
mixing
elbow.
When
the
compressor
is
below
the
evaporator,
the
riser
position.
3.
Size
the
suction
line
from
the
evaporator
through
the
riser
for
high
velocity.
Enter
the
suction
pipe
sizing
charts
in
the
Carrier
System
Design
Manual
at
design
tons
and
equivalent
length
(for
2
degree
F
loss).
If
reading
falls
between
2
sizes
on
chart,
choose
the
smaller
pipe
size.
at
the
evaporator
does
not
have
to
extend
as
high
as
the
top
level.
After
a
15-diameter
riser
has
been
provided,
the
suction
line
may
elbow
down
immediately.
SAFETY
RELIEF
A
fusible
plug
is
located
on
unit
liquid
line
before
the
liquid
valve.
z<