EasyManua.ls Logo

Carrier 38AK024-044 - Timer Functions; Sequence of Operation; Complete Unit Stoppage

Carrier 38AK024-044
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Timer
Functions
(See
Fig.
14)
1.
Switch
A
(contacts
A-AI
and
A-A2)
provides
Time
Guard
Control
Circuit
function.
Start
of
compressor
is
delayed
approximately
5.5
minutes
after
shut-off.
The
minimum
time
between
starts
of
compressor
is
8
minutes.
2.
Switch
B
(contacts
B-B1
and
B-B2)
starts
compressor.
3.
Switch
D
(contacts
D-D1)
bypasses
the
low-pressure
switch
(LPS)
for
2.5
minutes
at
start-up
for
winter
start
control.
TIMER
POSITION
DURING
UNIT
OPERATION
EMEN
150
SEC
+5
5.5
MINA/——.
KA
—-1--—-———————
COMPRESSOR
STARTS
A-A2
=
12
SEC
#2
|
B-BI
—{
———
—»
}e—1SEC
20.5
|
B-B2
_stia
5
SEC
+2
—EEl
———
e
40
SEC
$5
|
r_n
cr
D-DI
Ç]
|<
2-6
SEC
<
2-6SEC
a
awOcacvvsc
D-D2
ER
oe
===
150
SEC
#5
55
MINS/—-
Fig.
14
Timer
Cycle
(BLACK
DENOTES
CLOSED
CONTACTS)
OMIN
OR
Sequence
of
Operation
At
start-up,
the
thermostat
calling
for
cooling
and
all
safety
devices
satisfied,
the
control
circuit
relay
(CR1)
closes.
The
indoor
fan
motor
starts
imme-
diately.
With
minimal
demand
for
cooling,
only
ТСІ
of
the
thermostat
is
made.
The
timer
motor
starts
and
condenser
fan
no.
1
starts.
Fan
no.
2
starts
if
high
side
pressure
is
higher
than
260
psig
(1793
kPa).
Fan
no.
3
(38AK044
only)
starts
if
outdoor
ambient
rises
above
80
F.
After
a
delay
by
Time
Guard?
circuit
of
12
seconds
to
approximately
8
minutes
depending
on
the
timer
position,
the
compressor
starts
and
the
primary
liquid
line
solenoid
valve
opens.
With
only
TCI
calling
for
cooling,
the
capacity
control
liquid
line
solenoid
is
not
energized,
therefore
the
suction
pressure
is
such
that
the
compressor
unloads
on
suction
pressure
shortly
after
compressor
start-up.
The
compressor
operates
at
either
1
or
2
steps
of
unloading
depending
on
the
suction
pressure
which
is,
in
turn,
dependent
on
the
evaporator
load
conditions.
As
cooling
demand
increases,
TC2
of
the
2-stage
thermostat
energizes
the
capacity
control
liquid
line
solenoid
causing
full
surface
of
the
evaporator
to
be
active,
tending
to
raise
the
suction
pressure
so
that
the
compressor
loads.
16
A
pump-out
relay
(POR)
in
the
control
circuit
is
energized
when
thermostat
contacts
make.
A
set
of
normally
open
POR
contacts
close,
completing
a
compressor
control
circuit
which
bypasses
the
СКІ
contacts.
As
cooling
demand
is
satisfied,
the
thermostat
contacts
break,
de-
energizing
CR1.
The
LLS
valve
closes,
stopping
the
flow
of
liquid
refrigerant
to
the
evaporator
and
subsequent
suction
gas
to
the
compressor.
The
compressor
continues
to
operate
because
of
the
CRI
bypass
with
relay
TRI.
With
no
refrigerant
returning
to
the
compressor,
low
side
pumpout
takes
place
and
the
compressor
shuts
down
on
low-pressure
control.
The
compressor
does
not
restart
until
the
thermo-
stat
again
calls
for
cooling.
Complete
Unit
Stoppage
CAUSES
Interruption
of
supplied
power,
open
discharge
gas
thermostat
(DGT),
compressor
overtemperature
pro-
tection,
or
open
high-pressure
safety
switch
causes
com-
pressor
stoppage.
RESTART
The
unit
recycles
and
restarts
automatically
under
the
Time
Guard®
device
when
power
is
restored.
Stoppage
by
DGT,
HPS,
or
compressor
circuit
breaker
requires
manual
resetting
of
the
control
circuit.
To
restart
the
Time
Guard
timer
when
DGT
or
HPS
are
tripped,
merely
open
and
then
close
the
thermostat
contacts.
It
is
necessary
to
manually
reset
the
compressor
circuit
breaker
at
the
unit.
If
LPS
is
not
closed
within
2.5
minutes
after
compressor
starts,
the
compressor
locks
out
and
the
outdoor
fans
continue
to
run.
It
stays
locked
out
for
5.5
minutes
until
the
timer
motor
comes
back
to
0
time
(see
Fig.
14).
At
0
time,
the
LPS
is
jumpered
(winter
start
control).
It
remains
jumpered
for
2.5
minutes.
Because
the
LPS
is
jumpered,
the
com-
pressor
restarts
and
runs
for
the
2.5-minute
time
period.
At
the
end
of
this
2.5
minutes,
if
the
LPS
has
still
not
closed,
the
compressor
is
again
locked
out.
The
timer
motor
is
de-
energized
and
cannot
restart
until
the
LPS
closes.
The
outdoor
fans
continue
to
run
as
long
as
there
is
a
call
for
cooling.
Automatic
reset
of
the
LPS
causes
the
timer
to
recycle
so
that
the
compressor
can
start.
If
sufficient
compressor
oil
pressure
has
not
been
built
within
2.5
minutes
after
the
compressor
starts,
the
unit
is
completely
de-energized
until
the
OPS
is
manually
reset
at
the
unit.
A
CAUTION
If
unit
or
circuit
stoppage
occurs
more
than
once
due
to
any
safety
device,
the
trouble
should
be
corrected
before
any
attempt
to
restart.

Related product manuals