Placing
Unit
There
must
be
4
ft
(1220
mm)
for
service
and
for
unrestricted
airflow
on
all
sides
of
unit,
and
a
minimum
of
8
ft
(2440
mm)
clear
air
space
above
unit.
For
multiple
units,
allow
8
ft
separation
between
units
for
airflow
and
service.
Mounting
Unit
When
unit
is
in
proper
location,
use
of
mounting
holes
in
base
rails
is
recommended
for
securing
unit
to
supporting
structure,
or
for
mounting
unit
on
vibration
isolators
if
required.
Fasteners
for
mounting
unit
are
field
supplied.
Be
sure
to
mount
unit
level
to
ensure
proper
oil
return
to
compressors.
Compressor
Mounting
As
shipped,
compressor
is
held
down
by
4
bolts.
After
unit
is
installed
loosen
each
bolt
until
the
snubber
washer
can
be
moved
with
finger
pressure.
See
Fig.
3.
x
SNUBBER
SELF
OUR
WASHER
NEOPRENE
SNUBBER
COMPRESSOR
FOOT
ISOLATION
SPRING
Fig.
3
Compressor
Mounting
INSTALLATION
Refrigerant
Piping
Connections
Line
sizes
depend
on
length
of
piping
required
between
condensing
unit
and
evaporator.
See
Table
2.
It
is
important
to
consider
liquid
lift
and
compressor
oil
return.
Refer
to
Part
3
of
Carrier
System
Design
Manual
for
line
sizing
information,
and
Fig.
4
for
recommended
piping
details.
COIL
END RED
RED
CENTER
ELL
LINE
TO
COMPRESSOR
У
е
(VIA
DOUBLE
SUCTION
RISER
IF
NECESSARY)
UPPER
SECTION
AIR~
FLOW
TXV
SENSING
BULB
MIDDLE
SECTION
AIR-
FLOW
LOWER
SECTION
8
DIAM
MIN
TYP
ЖТ
XV
EQUALIZER
CONNECTION
NOTES:
1
Suction
line
is
connected
to
coil
on
same
side
as
the
entering
air.
2
Forcoilshaving
only
one
section,
use
upper
section
piping;
for
coils
having
2
sections,
use
upper
and
middle
section
piping
3
Lower
section
is
first
on
and
last
off.
4
For
more
complete
piping
information,
refer
to
Carrier
System
Design
Manual,
Part
3
Fig.
4
Suction
Line
Piping
to
Unit
with
3
Section
Coil
Split
Single
Pumpout
Control
All
units
are
factory
wired
to
operate
on
single
pumpout
control.
A
factory-supplied
liquid
line
solenoid
valve
must
be
installed
in
the
liquid
line
ahead
of
the
indoor
coil.
See
Fig.
5.
Wires
from
solenoid
valve
must
be
in
conduit,
and
a
ground
wire
must
be
provided
to
comply
with
codes.
À
WARNING
Failure
to
properly
install
liquid
line
solenoid
at
the
indoor
unit
as
described,
without
Carrier
author-
ization,
may
VOID
warranty.
If
unit
is
used
with
a
chiller,
wiring
modifications
may
be
required.
Filter
Drier
And
Moisture
Indicator
Every
unit
should
have
a
filter
drier
and
a
sight
glass
(moisture
indicator)
field
installed.
Select
the
filter
drier
for
maximum
unit
capacity
and
minimum
pressure
drop.
Figure
5
shows
recommended
locations
of
filter
drier(s)
and
sight
glass.
Complete
the
refrigerant
piping
from
the
evaporator
to
the
condenser
before
opening
the
liquid
and
suction
lines
at
the
condensing
unit.
One
filter
drier
may
be
installed
at
location
A
in
Fig.
5,
or
2
filter
driers
may
be
installed
at
locations
B.
`
FACTORY
SUPPLIED
FIELD
SUPPLIED
SOLENOID
VALVE
CAPACITY
CONTROL
SIGHT
SOLENOID
VALVE
2
FILTER
DRIERS
FILTER
DRIER
B
LOCATIONS
A
LOCATION
INDOOR
EVAPORATOR
L
COI
CIRCUIT
2
DISTRIBUTOR
Fig.
5
Liquid
Line
Solenoid
Valve,
Filter
Drier(s)
and
Sight
Glass
Locations
Receiver
No
receiver
is
provided
with
the
unit;
it
is
recommended
that
one
not
be
used.
Piping
Procedure
Do
not
remove
run-around
pipe
from
suction
and
liquid
line
stubs
until
piping
connections
are
ready
to
be
made.
Pass
nitrogen
or
other
inert
gas
through
piping
while
brazing,
to
prevent
formation
of
copper
oxide.
Install
field-supplied
thermostatic
expansion
valve
in
liquid
line
ahead
of
each
evaporator
section.
For
2-step
cooling,
the
field-supplied
solenoid
used
must
be
wired
to
be
opened
by
control
from
a
2-step
thermostat.
For
example:
2
solenoids
may
be
used
with
3
TX Vs
—one
of
the
solenoids
serving
a
liquid
line
feeding
2
of
the
TXVs.

Related product manuals