EasyManua.ls Logo

Carrier 38AK024-044 - Oil Pressure Safety Switch (OPS); Compressor Protection; High-Pressure Switch; Low-Pressure Switch

Carrier 38AK024-044
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Oil
Pressure
Safety
Switch
(OPS)
in
the
control
circuit
stops
the
compressor,
and
unit,
if
proper
oil
pressure
differential
is
not
established
at
start-up
or
maintained
during
operation.
If
OPS
stops
the
unit,
determine
the
cause
and
correct
before
restarting
unit.
Failure
to
do
so
will
constitute
abuse.
Equipment
failure
due
to
abuse
may
void
the
Warranty.
Compressor
Protection
CIRCUIT
BREAKER
Calibrated
trip
manual
reset,
ambient
compensated,
magnetic
breaker
protects
against
motor
overload
and
locked
rotor
conditions.
DISCHARGE
THERMOSTAT
A
sensor
in
the
dis-
charge
gas
of
06E
compressor
reacts
to
excessively
high
discharge
gas
temperature
and
shuts
off
the
compressor.
TIME
GUARDS
control
protects
compressor
against
short
cycling.
See
Sequence
of
Operation
(page
16).
CRANKCASE
HEATER
minimizes
absorption
of
liquid
refrigerant
by
oil
in
crankcase
during
brief
or
extended
shutdown
periods.
Control
circuit
is
maintained
if
com-
pressor
fan
motor
circuit
breakers
are
turned
off.
Main
disconnect
must
be
on
to
energize
crankcase
heater.
IMPORTANT:
Never
open
any
switch
or
disconnect
that
de-energizes
the
crankcase
heater
unless
unit
is
being
serviced
or
is
to
be
shut
down
for
a
prolonged
period.
After
a
prolonged
shutdown
on
a
service
job,
energize
the
crankcase
heater
for
24
hours
before
starting
the
compressor.
High-Pressure
Switch
has
fixed,
nonadjustable
set-
tings.
Switch
is
mounted
on
the
compressor.
TO
CHECK
Open
the
condenser
fan
circuit
breaker.
Head
pressure
builds
up
until
compressor
shuts
down.
This
should
be
at
the
cutout
pressure
in
Table
4.
Close
condenser
fan
circuit
breaker.
After
pressure
drops
to
cut-in
setting,
reset
control
circuit
by
opening,
then
closing
the
control
circuit
switch.
After
control
circuit
is
reset,
the
Time
Guard
timer
cycles
and
in
approximately
5.5
minutes
the
com-
pressor
restarts.
19
Low-Pressure
Switch
has
fixed,
nonadjustable
settings.
Switch
is
mounted
on
the
compressor.
TO
CHECK
Slowly
close
liquid
shutoff
valve
and
allow
compressor
to
pump
down.
Do
not
allow
compressor
to
pump
down
below
2
psig
(13.8
kPa).
Compressor
should
£
:
shut
down
when
suction
pressure
drops
to
cutout
pressure
in
%
,
Table
4,
and
should
restart
when
pressure
builds
up
to
cut-In
pressure
shown.
Table
4
Pressure
Switch
Settings,
psig
(kPa)
HIGH
PRESSURE
Cutout
|
Cutin
|
426
+
7
320
+
20
(2206
+
138)
Winter
Start
Control
Switch
D
in
the
4-function
(2937
+
48)
timer
bypasses
low-pressure
switch
for
21^
minutes
on
unit
start-up.
LOW
PRESSURE
27
+3
(186
+
21)
44
+
5
(303
+
34)
Head
Pressure
Control
reduces
condensing
capacity
under
low
ambient
temperature
conditions.
FAN
CYCLING
These
38AK
units
have
standard
provision
for
fully
automatic
intermediate-season
head
pressure
control
through
condenser
fan
cycling.
Fan
no.
2
is
cycled
by
a
fan
cycling
pressure
switch
(FCPS)
which
responds
to
variation
in
discharge
pressure.
The
pressure
sensor
is
located
in
the
liquid
line
of
the
refrigerant
circuit.
Fan
no.
3
cycling
is
controlled
by
outdoor
air
temperature
through
an
air
temperature
switch
(ATS)
(38AK044
units
only).
The
ATS
is
located
in
the
lower
divider
panel
between
the
.
compressor
compartment
and
condenser
section.
Through;
a
hole
in
the
panel,
the
sensing
element
is
exposed
to
air
entering
the
no.
1
fan
compartment.
Fan
no.
1
is
non-
cycling.
Table
5
shows
the
operating
settings
of
the
fan
cycling
pressure
switch
and
the
air
temperature
switch.
Table
5
Fan
Cycling
Controls
CONTROL
BY
SWITCH
OPENS
SWITCH
CLOSES
70
X
3
(21
t
1.7
160
+
10
(1103
+
69)
Pressure,
psig
(kPa)
260
+
15
(1793
+
103)
NOTE:
See
Fig.
6,
7,
8
for
fan
arrangement

Related product manuals