Carrier 38AK024-044 - Field Connections; Main Power; 24-v Control Power; Control Circuit Interlock

Carrier 38AK024-044
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.
Maximum
field
wire
sizes
allowed
by
lugs
on
terminal
UNBALANCED
3-PHASE
SUPPLY
VOLTAGE
block
are:
Never
operate
a
motor
where
a
phase
imbalance
in
supply
350
MCM
for
models
38AK028
(208/230-3-60),
voltage
is
greater
than
2%.
Use
the
following
formula
to
38AK034
(208
/230-3-60,
230-3-50),
and
determine
the
%
voltage
imbalance:
38AK044
(208/
230-3-60,
230-3-50)
2/0
AWG
for
all
other
models.
5.
Terminals
for
field
power
supply
are
suitable
for
copper,
copper-clad
aluminum
or
aluminum
conduc-
96
Voltage
Imbalance
max
voltage
deviation
from
average
voltage
tors.
Insulation
must
be
rated
167
F
(75
C)
minimum.
=
НЮ
average
voltage
CONDENSER
FANS
The
fans
must
rotate
counter-
.
clockwise
when
viewed
from
above.
If
necessary,
correct
Example:
Supply
voltage
is
240-3-60.
direction
of
fan
rotation
by
interchanging
any
2
power
|
input
wires
at
disconnect
switch.
Affix
crankcase
һеаїег
^
B
C
AB-
243
volts
decal
(located
in
installer's
packet)
to
unit
disconnect
switch.
BC
=
236
volts
AC
-
238
volts
FIELD
CONNECTIONS
1.
Main
Power
Bring
wires
from
the
fused
disconnect
switch
through
hole
in
bottom
rail
of
unit
to
control
Average
Voltage
=
box
(Fig.
6,
7,
8)
and
connect
terminals
; Г
оп
line
side
of
terminal
block
ТВІ
(see
Fig.
9).
To
comply
with
NEC
Article
440-14,
the
disconnect
а
Ee
within
sight
from
and
readily
acces
(AB)
243
-
239
š
4
volts
.
.
|
(ВС)
239
-
236
=
3
volts
:2.
24-v
Control
Power
Units
have
single
point
power
(AC)
239
-
238
=
1
volt
connections.
Control
circuit
is
directly
connected
inter-
nally
to
unit.
Maximum
24-v
control
circuit
is
3
amps.
243
+
236
+
238
=
239
volts
3
Determine
maximum
deviation
from
average
voltage:
Maximum
deviation
is
4
volts.
Determine
%
voltage
NOTE:
For
wire
runs
up
to
50
ft.
use
no.
18
AWG
imbalance:
insulated
wire
(35
C
min.).
For
50
to
75
ft.,
use
no.
16
AWG
insulated
wire
(35
C
min.).
For
over
75
ft.
use
14
»
4
_
AWG
insulated
wire
(35
C
min.).
as
сее
3.
Control
Circuit
Interlock
An
airflow
switch
may
be
installed
in
the
indoor
air
handler
to
prevent
unit
from
running
when
indoor
air
is
not
flowing.
This
switch
(no.
HRS81JEO01)
is
available
from
Service
Parts
Center,
or
This
amount
of
phase
imbalance
is
satisfactory
as
it
is
equivalentcan
be
field
supplied.
This
should
be
electri-
below
the
maximum
allowable
2%.
cally
interlocked
in
the
control
circuit,
between
term-
inals
[
1
|
and
[
6
]
(for
flow
switch)
on
TB2.
See
Fig.
9
for
field
wiring.
This
is
in
the
1
15-v
circuit.
Wires
must
IMPORTANT:
Contact
your
local
electric
utility
be
run
in
conduit
with
ground
wire.
company
immediately
if
the
supply
voltage
phase
4.
Transformer
Connections
See
unit
wiring
label
dia-
imbalance
is
more
than
2%.
gram,
notes
|
and
2,
located
behind
compressor
com-
partment
end
access
door.
IMPORTANT:
Ensure
power
to
the
crankcase
heater
is
always
on
(except
when
servicing
the
unit).
If
circuit
breakers
inside
unit
shut
down
the
com-
pressor
and
condenser
fans,
crankcase
heater
remains
on.