MOTORMASTER® CONTROL
(LOW AMBIENT KIT)
INSTALLATION
The accessory low-ambient kit contains a fan speed (Motor-
master) control device activated by a temperature sensor (Fig. 8).
The kit controls condenser fan motor speed in response to
the saturated condensing temperature. For outdoor tempera-
tures down to −20 F (−29 C), it maintains the condensing
temperature at 100 610 F (38 66 C).
The low-ambient (Motormaster) control consists of a solid-
state circuit on a printed circuit board encased in an alumi-
num extrusion. The control must be fastened to a panel in
the unit, and the sensor assembly (Fig. 8) mounted to a re-
turn bend on the unit’s condenser coil. Parts necessary for
mounting control and sensor are included in the kit.
Pre-Installation
DISCONNECT UNIT POWER To prevent electric shock,
open and tag all disconnects before modifying the condens-
ing unit.
INSTALL WINTER START CONTROL The unit must
be modified for winter start control before installing and us-
ing the low-ambient kit. Order Winter Start Control acces-
sory no. 38AE900021 and install according to the instruc-
tions supplied with the kit. See Fig. 9 for wiring.
FABRICATE AND INSTALL WIND BAFFLES The
38AKS units equipped with the low-ambient kit require baffles
to prevent wind crosscurrents from causing abnormal opera-
tion as the fan is modulated. Construct and install wind baffles
as shown in Fig. 10.
VERIFY POWER WIRING Power wiring must comply
with NEC (National Electrical Code) and all requirements.
Confirm that supply voltage meets minimum voltage speci-
fied on the unit’s rating plate and that it matches the voltage
rating of the low-ambient kit.
LEGEND
C—Contactor
HPS High-Pressure Switch
IP Internal Protector
LPS Low-Pressure Switch
TDR Time-Delay Relay
Field-Supplied Wiring
Fig. 9 Connection Points, Time-Delay Relay,
Accessory Winter Start Package 38AE900021
KIT NO. VOLTS AMPS A B C
32LT900301 All except 460 8.0 5
7
8
6
3
16
3
3
8
32LT900611 460 4.0 5
7
8
7
3
8
3
3
8
Fig. 8 Low-Ambient (Motormaster) Control and
Sensor Assembly
LOW-AMBIENT
CONTROL
SENSOR