EasyManua.ls Logo

Carrier 38AUM Series - Compressor Protection Systems; Crankcase Heater Functionality

Carrier 38AUM Series
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table CADM Troubleshooting
Miswired Module Indication
Recommended Troubleshooting
Action
Green
LED
is not on, module
does not power up
Determine if both R and C module terminals are connected. Verify voltage in present at module’s R
and C terminals.
NOTE: The
CADM
requires a constant nominal
24VAC
power supply. The wiring to the module’s R
and C terminals must be directly from the control transformer. The module cannot receive its
p
o
wer
from another
device that will interrupt the
24VAC
power supply. See the
38AU
Wiring Diagram(s) (Fig. 30 and Fig. 31).
Green
LED
Intermittent,
module powers up only
when compressor runs
Determine if R and Y terminals are wired in
reverse.
Verify module’s R and C terminals have a con
-
stant source.
See NOTE above for details on R and C
wir
in
g
.
TRIP LED
is on but system
and compressor check OK
Verify Y terminal is wired properly per the
38AU
wiring diagram (see Fig. 30 and Fig. 31). Verify voltage at
contactor coil falls below
0.5VAC
when off. Verify
24VAQC
is present across Y and C when thermostat demand
signal is present. If not, R and C are
reverse
wired.
TRIP LED
and
ALERT
LED
flashing
t
oge
ther
Verify R and C terminals are supplied with 19-28VAC.
ALERT
Flash Code 3
(Compressor Short
C
yclin
g
)
displayed
i
nco
rre
ctly
Verify Y terminal is connected to
24VAC
at contactor coil. Verify voltage at contactor coil falls
b
e
lo
w
0.5VAC
when off.
ALERT
Flash Code 5 or 6 (Open
Circuit, Missing Phase)
displayed
i
nco
rre
ctly
Check that compressor T1 and T3 wires are through module’s current sensing holes. Verify Y ter- minal is
connected to
24VAC
at contactor coil. Verify voltage at contactor coil falls below 0.5VAC when off.
Alert Flash Code
*
(Welded
C
on
ta
ctor
)
displayed
i
nco
rre
ctly
Determine if module’s Y terminal is connected. Verify Y terminal is connected to
24VAC
at con
t
a
ctor coil. Verify
24VAC
is present across Y and C when thermostat demand signal is present. If not, R and C are
reverse
wired.
Verify voltage at contactor coil falls below
0.5VAC
when off.
Compressor Protection
Compressor Overtemperature Protection (IP) A thermostat installed on the compressor motor winding
reacts to excessively high winding temperatures and shuts off the compressor.
Crankcase Heater The heater minimizes absorption of liquid refrigerant by oil in the crankcase during brief or
extended shutdown periods. The heater is wired to cycle with the compressor; the heater is off when compressor is
running, and on when compressor is off. The crankcase heater will operate as long as the power circuit is energized.
The main disconnect must be on to energize the crankcase heater.
Advanced Scroll Temperature Protection (ASTP) See “Advanced Scroll Temperature Protection (ASTP)”
Low-Pressure Switch The 38AUM low-pressure switch is stem-mounted on the suction line. Switches are all fixed,
non-adjustable type.
High--Pressure Switch The high--pressure switch is stem mounted on the discharge line. The switch is a fixed,
non-adjustable type.
Outdoor Fans Each fan is supported by a formed-wire mount bolted to the fan deck and covered with a wire guard.
Fan motors have permanently lubricated bearings.
1. Shut off unit power supply. Install lockout tag.
2. Remove outdoor fan assembly (grille, motor, and fan).
3. Loosen fan hub setscrews.
4. Adjust fan height.
5. Tighten setscrews to 84 in-lbs (949 N-cm).
6. Replace outdoor fan assembly.
Fig: - Outdoor Fan Blade Position
IMPORTANT: Never open any switch or disconnect that energizes the crankcase heater unless
unit is being serviced or is to be shut down for a prolonged period. After a prolonged shutdown
on a service job, energize the crankcase heater for 24 hours before starting the compressor.
Page 26

Related product manuals