ELECTRICAL DATA TABLE
MIN MAX RLA LRA RLA LRA HP FLA MCA MOCP
38AUMZ07 360 440 9.7 64 - - 1/4 0.7 13.5 20
38AUMZ08 360 440 12.2 100 - - 1/3 1.8 18.9 30
MIN MAX RLA LRA RLA LRA HP FLA MCA MOCP
38AUMD12 360 440 7.8 51.5 7.8 51.5 1/3 1.8 21.2 25
38AUMD14 360 440 10.6 74 10.6 74 1/3 1.8 27.5 35
38AUMD16 360 440 12.2 101 12.2 101 1/2 1.7 30.9 40
Legend and Notes for Electrical Data Table
NEC - National Electrical Code
OFM - Outdoor (Condenser) Fan Motor
HACR - Heating, Air-Conditioning and Refrigeration
◊ Fuse or HACR Circuit Breaker
Application heater kW (Using multiplication factor table in Electric Resistance Heater Data Table)
AB = 392v
BC = 404v
AC = 395v
1191
3
(AB) 397 - 392 =5v
(BC) 404 - 397 =7v
(AC) 457 - 397 =2v
7
397
FLA - Full Load Amps
= 100 X
IFM - Indoor (Evaporator) Fan Motor
LRA - Locked Rotor Amps
MCA - Minimum Circuit Amps
MOCP - Maximum Overcurrent Protection
Example: Supply Voltage is 400V - 3ph - 60Hz
Maximum Deviation From Average Voltage
Average Voltage
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%
IMPORTANT: If the supply voltage phase imbalance is more than 2% contact your local electric utility company
Never operate a motor where phase imbalance in supply voltage is greater than 2%.
Use the following formula to determine the percentage of voltage imbalance
Determine Percentage Voltage Imbalance.
Single Circuit Unit - 400V-3Ph-50Hz
Dual Circuit Unit - 400V-3Ph-50Hz
POWER SUPPLY
V-Ph-Hz
VOLTAGE RANGE COMP 1 COMP 2
POWER SUPPLY
Unit
VOLTAGE RANGE COMP 1 COMP 2 OFM (ea)
OFM (ea)
Unbalanced 3-Phase Supply Voltage
392 + 404 + 395
Average Voltage =
3
= 100 X
% Voltage Imbalance
Determine maximum deviation from average voltage.
= 397V
= 1.76%
Maximum Deviation is 7v.