Table 4 -  Refrigerant  Charge Adjustments 
 
Liquid Line 
Size
  Puron Charge 
(oz/
ft
)
 
3/8  0.60 (Factory charge for lineset = 13.5 oz (382.7) 
5/16
  0.40 
1/4
  0.27 
Units are factory charged for 25 ft (7.6 m) of 3/8” liquid line.  The factory charge for 3/8” lineset 9 oz (266.2 g).  When using other length or 
diameter liquid lines, charge adjustments are required per the chart above. 
Charging Formula: 
[(Lineset oz/ft x total length) – (factory charge for lineset)] = charge adjustment 
 
Example 1: System has 25ft of line set using existing 1/4“liquid line.  What charge adjustment is required? 
Formula: (.27 oz/ft x 25ft) – (13.5 oz) = -6.75 oz; (8.0 g/m x 7.6 m) – (382.7 g) = -321.9 g 
Net result is to remove 6.75 oz of refrigerant from the system 
Example 2: System has 45 ft of existing 5/16” liquid line. What is the charge adjustment? 
Formula: (.40 oz/ft. x 45ft) – (13.5 oz.) = 9 oz; (11.8 g/m x 13.7m) – (382.7 g) = -221.0 g 
Net result is to add 4.5 oz of refrigerant to the system 
 
 
 
 
 
LSV (Heat  Pump 
Only)
 
 
 
 
 
 
 
 
 
Fig.  2 – Equal– Level  Outdoor/Indoor  Unit 
•  A TXV with 15 to 30% bleed must be installed at indoor unit when application  qualifies  as long line. See Table 6. 
•  Hard Start  Kit (start capacitor and relay)  must be installed on outdoor  unit when application  qualifies  as long line. See Table 6. 
•  A crankcase heater must  be installed  on compressor  when the application  qualifies  as long line.   See Table 6 . 
•  Vapor line should slope towards  indoor unit. 
•  Maximum  actual liquid line is up to 100 (61 m).   See Table 5. 
•  Maximum  total equivalent  length is up to 120 (76.2 m).   See Table 5. 
•  Heat pump only – Bi- flow liquid line solenoid  must be installed within 2 ft (0.61 m) of outdoor unit with arrow pointing towards 
outdoor  unit. 
• 
Heat pump only – Outdoor  AccuRater
TM
 adjustment  not required
 
•  Use vapor line per Tables  3. 
•  Use liquid lines per Table 5. 
Table 5 –  Maximum Total Equivalent  Length 
Equal Level or Outdoor Unit Below Indoor 
 
 
Size
 
 
System 
Ty
pe
 
Liquid 
Line 
Diameter 
w/ TX
V
 
Maximum  Total  Equivalent  L
e
n
g
th**
:
 Outdoor  unit BELOW 
I
n
door
 
Vertical  Separation  ft 
(
m
)
 
0
 
---
 
5 
(0
 
---
 
1.
5)
 
6
 
---
 
10 
(1.8 
---
 
3.
0)
 
11 
---
 
20 
(3.4 
---
 
6.
1)
 
21 
---
 
30 
(6.4 
---
 
9.
1)
 
31 
---
 
40 
(9.4 
---
 
12.
2)
 
41 
---
 
50 
(12.5 
---
 
15.
2)
 
51 
---
 
60 
(15.5 
---
 
18.
3)
 
61 
---
 
70 
(18.6 
---
 
21.
3)
 
71 
---
 
80 
(21.6 
---
 
24.
4)
 
18000 
AC 
Only
 
1/4
 
150*
 
150*
  125  100  100  75  --- 
---
  --- 
---
  --- 
---
 
AC 
Only
 
5/16
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
  150 
AC/HP 
3/8
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
 
24000 
AC 
Only
 
1/4
  75  75  75  50  50  --- 
---
  --- 
---
  --- 
---
  --- 
---
 
AC 
Only
 
5/16
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
  125  100 
AC/HP 
3/8
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
 
30000 
AC 
Only
 
1/4
  30  --- 
---
  --- 
---
  --- 
---
  --- 
---
  --- 
---
  --- 
---
  --- 
---
  --- 
---
 
AC 
Only
 
5/16
 
150*
 
125*
  100  150  125  100  75  --- 
---
  --- 
---
 
AC/HP 
3/8
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
 
36000 
AC 
Only
 
5/16
 
150*
 
150*
 
150*
  100  100  100  75  --- 
---
  --- 
---
 
AC/HP 
3//8
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
48000 
AC/HP 
3/8
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
  --- 
---
 
60000 
AC/HP 
3/8
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
 
150*
  --- 
---
  --- 
---
 
* 
Maximum  actual  length  not to exceed  100ft 
** 
Total  equivalent  length  accounts  for losses  due  to elbows  or fitting.  See  the  Table  2 for 
de
tails. 
--- --- 
= 
outside  acceptable  r
a
n
ge