EasyManuals Logo

Carrier 38C Series User Manual

Carrier 38C Series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
Table 6 AC / HP with Puron® Refrigerant Long Line Description ft (m)
Beyond these lengths, long line accessories are required
AC
AC Liquid Line
Size
Units On Same
L
evel
1/4
No accessories needed within allowed
lengths
5/16
120 (36.6)
3/8
80 (24.4)
HP
HP Liquid Line
Size
Units On Same
L
evel
3/8
80 (24.4)
See Table 8 f or
Maximum
Height and
Equivalent
Length
Fig. 3 Outdoor Unit Below Indoor Unit
Unit must be charged to 10° subcooling or nameplate subcooling, whichever is greater.
A TXV with 15 to 30% bleed must be installed at indoor unit when application qualifies as long line. See Table 8.
A crankcase heater must be installed on compressor when the application qualifies as long line. See Table 8.
Hard Start Kit (start capacitor and relay) must be installed in outdoor unit when the application qualifies as long line. See Table 8.
An inverted vapor- line trap must be installed at indoor unit. The top peak of trap must be greater than height of indoor coil.
Ma
ximum actual liquid line length is up to See Table 7 for maximum total equivalent length.
Heat pump only Bi- flow liquid line solenoid must be installed within 2 ft (0.61 m) of outdoor unit with arrow pointing towards outdoor unit.
Heat pump only Adjust outdoor piston per Table 9.
Use vapor line per Tables 3.
Use liquid lines per Table 7.
Table 7 - Maximum Total Equivalent Length
**
Outdoor Unit Below Indoor Unit
Size
System
Ty
pe
Liquid
Line
Diameter
w/ TX
V
Maximum Total Equivalent L
e
n
g
th
{
:
Outdoor unit BELOW
I
n
door
Vertical Separation ft
(
m
)
0
---
5
(0
---
1.
5)
6
---
10
(1.8
---
3.
0)
11
---
20
(3.4
---
6.
1)
21
---
30
(6.4
---
9.
1)
31
---
40
(9.4
---
12.
2)
41
---
50
(12.5
---
15.
2)
51
---
60
(15.5
---
18.
3)
61
---
70
(18.6
---
21.
3)
71
---
80
(21.6
---
24.
4)
18000
AC Only
1/4
150 150 125 100 100 75 ---
---
---
---
---
---
AC Only
5/16
150*
150*
150*
150*
150*
150*
150*
150*
150
*
AC/HP
3/8
150*
150*
150*
150*
150*
150*
150*
150*
150*
24000
AC Only
1/4
75 75 75 50 50 ---
---
---
---
---
---
---
---
AC Only
5/16
150*
150*
150*
150*
150*
150*
150
*
125 100
AC/HP
3/8
150*
150*
150*
150*
150*
150*
150*
150*
150*
30000
AC Only
1/4
30 ---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
AC Only
5/16
150
*
150*
150*
150*
125 100 75 ---
---
---
---
AC/HP
3/8
150
*
150
*
150
*
150
*
150
*
150
*
150
*
150
*
150
*
36000
AC Only
5/16
150
*
150
*
150
*
100 100 100 75 ---
---
---
---
AC/HP
3//8
150
*
150
*
150
*
150
*
150
*
150
*
150
*
150
*
150
*
48000
AC/HP
3/8
150*
150*
150*
150*
150*
150*
150*
150*
---
---
60000
AC/HP
3/8
150*
150*
150*
150*
150*
150*
110 ---
---
---
---
*
Maximum actual length not to exceed 100ft
**
Total equivalent length accounts for losses due to elbows or fitting. See the Table 2 for
de
tails.
--- ---
=
outside acceptable range
Table 8 - AC / HP with Puro Refrigerant Long Line Description ft (m)
Beyond these lengths, long line accessories are required
AC
AC Liquid Line
Size
Outdoor Below
I
n
door
1/4
No accessories needed within allowed
lengths
5/16
50 (15.2) vertical or 120 (36.6)
to
ta
l
3/8
35 (10.7) vertical or 80 (24.4)
to
ta
l
HP
HP Liquid Line
Size
Outdoor Below
I
n
door
3/8
20 (6.1) vertical or 80 (24.4)
to
ta
l
Table 9 - Puron
®
Refrigerant Heat Pump Outdoor Piston Change Outdoor Unit BELOW Indoor Unit
Btuh
Vertical Separation ft (m) --- Outdoor BELOW Indoor
U
nit
)
0
---
19
(0
---
5.
8)
20
---
29
(6.1
---
8.
8)
30
---
39
(9.1
---
11.
9)
40
---
49
(12.2
---
14.
9)
50
---
59
(15.2
---
18.
0)
60
---
69
(18.3
---
21.
0)
70
---
80
(21.3
---
24.
4)
18,000 0
---
1
---
1
---
2
---
2
---
2
---
2
24,000 0
---
1
---
1
---
2
---
2
---
3
---
3
30,000 0
---
1
---
1
---
2
---
2
---
3
---
3
36,000 0
---
1
---
2
---
2
---
2
---
3
---
3
42,000 0
---
1
---
2
---
2
---
3
---
3
---
4
48,000 0
---
1
---
2
---
2
---
3
---
3
60,000
0
---
1
---
2
---
3
---
3
NOTE: (—) Indicates vertical separation exceeds allowable
limits.
Example 1: On a 4 ton system the outdoor unit is 60 ft (18.3 m) below the indoor unit. This is acceptable only if the total equivalent length is 230 ft (70.1 m)
o
r less.
The heating piston must be re
---
sized
---
3.
Example 2: On a 3
---
ton system the outdoor unit is 80 ft (24.4 m) below the indoor unit. This is acceptable up to 250 ft (76.2 m) total equivalent length.
T
he
heating piston must be re
---
sized
---
3.
Page 28

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier 38C Series and is the answer not in the manual?

Carrier 38C Series Specifications

General IconGeneral
BrandCarrier
Model38C Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals