TROUBLESHOOTING CONTINUED
(2) PFC protection malfunction
Main checking points: 
● 
● 
Is the power supply correct?;
Is the reactor broken or mis-wired? ;
Flow chart: 
Start
Verify that the power supply is 
correct
Power supply is not correct l
yes
yes
yes
no
no
no
Check if the outdoor reactor is broken
or mis-wired 
The reactor is broken
or mis-wired
Replace the reactor 
or correct the wiring 
Replace the outdoor
mainboard
Malfunction is eliminated
End
Turn the system on after
the power supply error is
cleared