EasyManua.ls Logo

Carrier 38HD018 - System Charging and Service Tasks; Refrigerant Charging; Unit Start-Up Sequence; General Maintenance Safety

Carrier 38HD018
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
A
CAUTION
Charge
System
Release
holding
charge
into
sys¬
tem
by
opening
(backseating)
liquid
and
suction
line
service
valves.
Add
charge
amount
as
required
for
the
total
system.
See
Table
1.
For
indoor
sections
not
in¬
cluded
in
Table
1,
see
Refrigerant
Charging.
To
Start
Unit
Assuring
that
crankcase
heater
has
been
on
for
24
hours,
and
field
disconnect
is
closed,
set
room
thermostat
below
ambient.
Unit
compressor
starts
after
a
5-minute
delay
if
equipped
with
optional
Time
Guard®
11.
Operate
unit
for
15
minutes,
then
check
system
refrigerant
charge.
See
Refrigerant
Charging.
SERVICE
A
CAUTION
Before
performing
recommended
maintenance,
be
sure
unit
main
power
switch
is
turned
off.
Failure
to
do
so
may
result
in
electric
shock
or
injury
from
rotating
fan
blade.
Condenser
Fan
is
held
by
a
reinforced
wire
mount
which
clamps
the
fan
motor
in
position.
See
Fig.
8
for
proper
mounted
fan
position.
OUTSIDE
EDGE
OF
FAN
DECK
qo
B.a.anQQ
qqqqo
OUTSIDE
EDGE
OF
GRILLE
^^FAN
BLADE
1
I
DIMENSION
FROM
OUTSIDE
TOP
EDGE
OF
BLADE
TO
OUTSIDE
EDGE
OF
FAN
DECK
SEE
CHART
BELOW
UNIT
SIZE
38HD018
38HD024,030
38HD036,048,060
433"
(11
mm)
709"
(18
mm)
16"
(4
mm)
Fig.
8
Mounted
Fan
Positions
High
Pressure
Relief
Valve
is
located
in
com¬
pressor.
Relief
valve
opens
at
a
pressure
differential
of
approximately
450
±
50
psig
between
suction
(low
side)
and
discharge
(high
side)
to
allow
pressure
equalization.
Internal
Current
and
Temperature
Sensitive
Overload
resets
automatically
when
internal
com¬
pressor
motor
temperature
drops
to
a
safe
level
(over¬
loads
may
require
up
to
45
minutes
to
reset)
When
an
internal
overload
is
suspected
of
being
open,
check
by
using
an
ohmmeter
or
continuity
tester.
If
necessary,
refer
to
Carrier
Standard
System
Techniques
Manual,
Chapter
2,
for
complete
information.
Pumpdown
Procedure
The
system
may
be
pumped
down
in
order
to
make
repairs
on
low
side
with¬
out
losing
complete
refrigerant
charge.
1.
Attach
pressure
gage
to
suction
service
valve
gage
port.
2.
Frontseat
the
liquid
line
valve.
3.
Start
unit
and
run
until
suction
pressure
reaches
5
psig
(see
Caution).
4.
Shut
unit
off
and
frontseat
suction
valve.
5.
Vent
remaining
pressure.
38HD
unit
coils
hold
only
the
factory
designated
amount
of
refrigerant.
Additional
refrigerant
may
cause
units
to
relieve
pressure
through
internal
pressure
relief
valve
(indicated
by
a
sudden
rise
of
suction
pressure)
before
suction
pressure
reaches
5
psig.
If
this
occurs,
shut
off
unit
immediately,
frontseat
suction
valve
and
vent
remaining
pressure.
Filter
Drier
Whenever
the
moisture-liquid
indicator
shows
presence
of
moisture,
replace
filter
drier.
Refer
to
Carrier
Standard
Service
Techniques
Manual,
Chapter
1,
Refrigerants,
for
details
on
servicing
filter
driers.
High
-Pressure
Switch
This
switch,
located
on
discharge
line,
protects
against
high
discharge
pressures
caused
by
such
events
as
overcharge,
condenser
fan
motor
failure,
system
restriction,
etc.
It
opens
on
pressure
rise
at
about
426
psi.
If
system
pressures
go
above
this
setting
during
abnormal
conditions,
switch
opens.
Do
not
attempt
to
simulate
these
system
abnormalities,
as
high
pressures
pose
a
serious
safety
hazard.
High-pressure
switch
is
also
checked
with
an
ohmmeter
similar
to
check¬
ing
low-pressure
switch.
If
system
pressure
is
below
426
psi,
switch
shows
continuity.
It
is
replaced
in
same
manner
as
low-pressure
switch.
Observe
all
safety
precautions.
Low-Pressure
Switch
This
switch,
mounted
on
the
suction
line,
has
fixed
nonadjustable
settings.
TO
CHECK
Attach
pressure
gage
to
suction
service
valve
gage
port.
Slowly
close
liquid
shutoff
valve
and
allow
compressor
to
pump
down.
Do
not
allow
com¬
pressor
to
pump
down
below
2
psig
(13.8
kPa).
Com¬
pressor
should
shut
down
when
suction
pressure
drops
to
cutout
pressure
in
Table
2,
and
should
restart
when
pressure
builds
up
to
cut-in
pressure
shown
after
CLO
(Compressor
Lockout)
has
been
reset
and
optional
Time
Guard
has
completed
its
timing
cycle.
Crankcase
Heater
prevents
refrigerant
migration
and
compressor
oil
dilution
during
shutdown
when
com¬
pressor
is
not
operating.
If
crankcase
heater
is
de¬
energized
for
more
than
6
hours,
both
compressor
service
valves
must
be
closed.
Crankcase
heaters
come
in
2
basic
types:
wraparound
(bellyband)
type
that
is
wrapped
externally
around
com¬
pressor
shell,
and
insertion
type
that
is
inserted
into
compressor
oil
well
in
shell
of
compressor.
Both
types
are
in
this
family
of
units.
Crankcase
heater
is
powered
by
high-voltage
power
of
unit.
It
is
connected
across
the
line
side
of
the
contactor
and
operates
continually.
Use
extreme
caution
trouble¬
shooting
this
device
with
power
on.
Easiest
method
of
troubleshooting
is
to
apply
voltmeter
across
crankcase
heater
leads
to
see
if
heater
voltage
is
on.
Do
not
touch
heater.
Carefully
feel
area
around
crankcase
heater.
If
warm,
crankcase
heater
is
probably
functioning.
With
power
off,
and
heater
leads
disconnected,
check
across
leads
with
ohmmeter.
Do
not
look
for
a
specific
resistance
reading.
Check
for
resistance
or
an
open
circuit.
Change
heater
if
an
open
circuit
is
detected.
Service
Valves
The
service
valves
in
the
condensing
unit
come
from
the
factory
frontseated
This
means
the
refrigerant
charge
is
isolated
from
the
line
set
connec¬
tion
ports.
To
prevent
damage
to
the
valve,
use
a
wet
cloth
or
other
accepted
heat
sink
material
on
the
valve
before
brazing.
The
service
valves
must
be
backseated
(turned
counter¬
clockwise
until
seated)
before
the
service
port
caps
can
be
removed
and
hoses
of
gage
manifold
connected.
In
this
position,
refrigerant
has
access
from
and
through
outdoor
and
indoor
unit.
The
service
valve
cannot
be
8

Related product manuals