16
LONG-LINE GUIDELINE 
Table 1 – REQUIRED FIELD INSTALLED  
ACCESSORIES FOR AIR CONDITIONERS AND HEAT PUMP 
ACCESSORY
REQUIRED FOR
LOW-AMBIENT APPLICATIONS
(BELOW 55°F)
REQUIRED FOR
LONG-LINE 
APPLICATIONS*
(OVER 50 FT)
REQUIRED FOR
SEA COAST 
APPLICATIONS
(WITHIN 2 MILES)
Crankcase Heater
Yes Yes No 
Evaporator Freeze Thermostat
Yes No No 
Winter Start Control
Yes† No No 
Accumulator
No No No 
Compressor Start Assist 
Capacitor and Relay
Yes Yes No 
Low Ambient Controller,
MotorMaster™ Control,
or
Low-Ambient Pressure Switch
Yes No No 
Wind Baffle
See Low-Ambient Instructions  No  No 
Coastal Filter
No No Yes 
Support Feet
Recommended No Recommended 
Liquid-Line Solenoid Valve
or
Hard-Shutoff TXV
No 
See Long-Line 
Application 
Guideline 
No 
Ball-Bearing Fan Motor
Yes‡ No No 
Isolation Relay
Yes** No No 
*For tubing line sets between 50 and 175 ft, refer to Residential Split-System Long-Line Application Guideline. 
†Only when low-pressure switch is used. 
‡Required for Low-Ambient Controller (full modulation feature) and MotorMaster™ control only. 
** Required on Heat Pumps only.
This Long-Line Application Guideline applies 
to all Carrier residential air conditioner and 
heat pump split systems that have a nominal 
capacity of 18,000 to 60,000 Btuh. This 
guideline provides required system changes 
and accessories necessary for any residential 
product having piping requirements greater 
than 50 ft or installations where indoor unit is 
located above outdoor unit. 
This guideline is intended to cover applications 
outside the standard Installation Instructions. 
This guideline is for standard, single-speed 
products. For applications involving 2-speed 
products, refer to Step 6 first. 
NOTE: The presale literature for outdoor unit 
must be referred to in conjunction with this 
guideline. 
Step 1—Approved Systems 
Any residential indoor/outdoor unit 
combination listed in the outdoor unit presale 
literature is an approved system, EXCEPT the 
following: 
• Indoor coils with capillary-metering devices 
• All equipment less than nominal 18,000 Btuh 
• All 1/4-in. and 3/16–in. liquid-line 
applications 
• Any indoor furnace coil/fan coil not listed in 
outdoor unit presale literature 
• Any application which has interconnecting 
tubing with an equivalent length greater than 
175 ft 
Step 2—Interconnecting Tubing Sizing 
Table 2 lists recommended interconnecting 
vapor-line diameters for equivalent total-line 
lengths. All residential split systems installed 
in long-line applications must use only 3/8-in. 
liquid lines. Equivalent line length equals the 
linear length (measured) of interconnecting 
vapor tubing plus losses due to elbows. (See 
Table 3 and Fig. 3.) Liquid lines larger than 
3/8-in. OD greatly increase charge quantity of 
the system. Excessive charge increases risk of 
migration and compressor damage. Table 2 
provides the estimated percentage of nominal 
cooling-capacity losses based on the standard, 
required vapor line size versus what is selected 
for the long-line application. Since the vapor 
line is the discharge line in heating mode, 
losses are minimal. 
Calculate the linear length of vapor tube 
required, adding any losses for the total 
number of elbows for application. (See Table 
6.) Using this equivalent length, select desired