SG-38MHRC-01                                                                            Specifications subject to change without notice.                                 25
Evaporator Coil Temperature Protection
Fig. 29 — Evaporator Coil Temperature Protection
When the evaporator temperature is higher than the setting protection 
value, the compressor stops.
AUTO Mode
AUTO mode can be selected with the remote controller and the 
setting temperature can be changed between 60.0°F~86°F 
(16°C~30°C). 
In the AUTO mode, the unit chooses either COOLING, HEATING 
or the FAN-ONLY mode accT2, T4 and relative humidity.
Fig. 30 — AUTO Mode
Heating*: COOLING ONLY models run at fan speed. The indoor 
fan runs in the AUTO fan speed for the relevant mode. The louver 
operates the same as in the relevant mode.
If the unit switches mode between HEATING and COOLING, the 
compressor repeatedly stops for a certain time and then chooses the 
mode according to T1-Ts. If the setting temperature is modified, the 
unit selects a running function again. 
DRYING mode
The indoor fan speed is fixed at breeze and can not be changed. The 
louver angle is the same as in the COOLING mode. 
Low Indoor Room Temperature Protection
In the DRYING mode, if the room temperature is lower than 50°F 
(10°C), the compressor stops and does not resume until the room 
temperature exceeds 53.6°F (12°C).
Evaporator anti-freezing protection, condenser high temperature 
protection and outdoor unit frequency limit are active and are the 
same as that in the COOLING mode. The outdoor fan operates the 
same as in COOLING mode. 
FORCED OPERATION Function
Enter FORCED OPERATION function:
When the machine is off, press TOUCH to engage the Forced Auto 
Mode. Press TOUCH again, within 5 seconds, to engage the 
FORCED COOLING mode. In FORCED AUTO, FORCED 
COOLING or any other operation mode, press TOUCH to turn off 
the unit.
In the FORCED OPERATION mode, all general protections and the 
remote controller are available.
Operation Rules:
FORCED COOLING mode:
The compressor runs at the F2 frequency and the indoor fan runs as a 
breeze. After running for 30 minutes, the unit enters the AUTO mode 
at a 75.2°F (24°C) setting temperature.
FORCED AUTO mode: 
The FORCED AUTO mode is the same as the normal AUTO mode
with a 75.2°F (24°C) setting temperature.
AUTO-RESTART function
The indoor unit is equipped with an AUTO-RESTART function, 
which is carried out through an auto-restart module. In case of a 
sudden power failure, the module memorizes the setting conditions 
before the power failure. The unit resumes the previous operation 
setting (not including the swing function) automatically 3 minutes 
after the power returns. 
If the memorization condition is the FORCED COOLING mode, the
unit runs in the COOLING mode for 30 minutes and enters the
AUTO mode as 75.2°F (24°C) setting temp.
If the air conditioner turns off before the unit powers off and the air 
conditioner is required to restart immediately, the compressor delays 
for 1 minute when the power is on. Under other conditions, the 
compressor has a 3 minute delay when it restarts. 
Refrigerant Leakage Detection
With this new technology, the display area displays EC when the 
outdoor unit detects a refrigerant leak.
46°F (8°C) Heating
When the compressor is running, the indoor fan motor runs without 
the anti-cold air function. When the compressor is off, the indoor fan 
motor is off.