38MURA: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
13
8. Brazing Adapter (Optional)
When flare to braze adapter is used, follow these steps:
a. Refer to the liquid line and gas line connection O.D. sizes in 
Table 7 based on the model being installed. Cut and deburr the 
tubing (review “Remove the Burrs on page 11.) to prepare it 
for brazing. Setup the nitrogen apparatus and connect to the 
outside unit to flow nitrogen while brazing. Braze the tubing 
and any fittings to obtain a proper seal.
b. Adjust the nitrogen apparatus to pressurize the system. Pressure 
test the system to a maximum of 500 psig for at least 60 
minutes.
c. Insulate suction line completely, including the outdoor unit 
valves. 
9. Pressure Test Piping
NOTE: Use refrigeration gauges that are pressure rated for R410a 
refrigerant.
a. Attach low side gauge hose to the 5/16” Schrader valve 
on the outdoor unit service valve.
b. Attach the charging hose to the regulator on the dry nitrogen 
tank.
c. Preset the nitrogen regulator to 550 psi.
d. Slowly pressurize the line set until the low side gauge reads 500 
psi. Do not exceed 550 psi.
e. Close all the valves on the nitrogen tank and gauges.
f. Allow the pressure test to stand for a minimum of 30 minutes.
g. If the pressure holds, release the nitrogen and proceed with 
“Step 6 - Electrical Connections - Dip Switch Configuration on 
page 13.
h. If the pressure goes down in the 30 minute delay, leak check the 
tubing and flare fittings to identify the source of the leak. 
Return to Step C, above.
Additional Refrigerant Requirements
Step 6 - Electrical Connections - Dip Switch 
Configuration
Install All Power and Interconnecting Wiring to 
Outdoor Units
1. Mount the outdoor power disconnect.
2. Run the power wiring from the main box to disconnect per NEC and 
local codes.
3. Remove the field wiring cover from the unit by loosening the screws.
4. Remove the caps on the conduit panel. 
5. Connect the conduit to conduit panel (see Fig. 19).
6. Properly connect both the power supply and control lines to the 
terminal block per the connection diagram for the appropriate unit 
capacity and voltage.
7. Ground the unit in accordance with NEC and local electrical codes. 
8. Use the lock nuts to secure the conduit.
9. Reinstall the field wiring cover.
Fig. 19 —Field Wiring
System 
Size
Max. Piping Length with no 
additional refrigerant 
charge per System
Additional 
refrigerant 
charge 
Total Maximum 
Piping Length per 
system
ft. (m) Oz/ft (g/m) ft. (m)
18K
24.6 (7.5) 0.69 (65)
98 (30)
24K - 30K 164 (50)
36K - 60K 213 (65)
Only use Dry Nitrogen to pressure test refrigerant systems. Use of 
other gases can result in injury, property damage or death.
CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or 
improper operation.
Be sure to comply with local codes while running wire from 
indoor unit to outdoor unit. 
Every wire must be connected firmly. Loose wiring may cause the 
terminal to overheat or result in unit malfunction. A fire hazard 
may also exist. Therefore, ensure all wiring is tightly connected. 
No wire should be allowed to touch the refrigerant tubing, 
compressor or any moving parts. 
Disconnecting means must be provided and shall be located 
within sight and readily accessible from the air conditioner. 
Connecting cable with the conduit shall be routed through hole in 
the conduit panel.
CAUTION
Wire Cover 
Over 1.57in.(40mm)
Terminal block
Conduit panel
Conduit fitting
Connecting cable 
Select the appropriate conduit opening for the 
wire size used.
An approved and listed fitting must be used to securely affix 
conduit in accordance with NEC and local codes. 
WARNING