16
Detailed cooling capacities* continued
* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation and connected by 15 ft (4.57m) of tubing. If other than 15
ft (4.57m) of tubing is used and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.
Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
†† At TVA rating indoor condition (75˚edb/63˚ewb). All other indoor air temperatures are at 80˚edb.
Sensible capacities shown are based on 80˚F (27˚C) entering air at the indoor coil. For sensible capacities at other than 80˚F (27˚C), deduct 835
Btuh (245 kw) per 1000 cfm (480 L/S) of indoor coil air for each degree below 80˚F (27˚C), or add 835 Btuh (245 kw) per 1000 cfm (480 L/S) of
indoor coil air per degree above 80˚F (27˚C).
** System kw is total of indoor and outdoor unit kilowatts.
EWB = Entering wet bulb
EVAPORATOR AIR
CONDENSER ENTERING AIR TEMPERATURES
°
F
85 95 105 115
CFM EWB
Capacity
MBtuh†
Total
System
Kw**
Capacity
MBtuh†
Total
System
Kw**
Capacity
MBtuh†
Total
System
Kw**
Capacity
MBtuh†
Total
System
Kw**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡
38YKB060-30, 31 Outdoor Section With FB4AN(A,F,M)060 Indoor Section
1800
72 63.8 31.9 5.44 61.2 31.1 5.97 58.4 30.1 6.54 55.1 28.9 7.16
67 58.7 41.4 5.35 56.0 40.3 5.87 53.0 39.1 6.42 50.1 38.0 7.00
63†† 54.4 40.1 5.29 51.8 39.0 5.78 49.2 37.9 6.32 46.5 36.7 6.89
62 53.5 50.2 5.27 51.1 49.0 5.77 48.6 47.6 6.30 46.1 46.0 6.89
57 52.4 52.4 5.25 50.4 50.4 5.75 48.3 48.3 6.30 46.1 46.1 6.88
2000
72 64.4 33.0 5.55 61.9 32.2 6.08 59.0 31.3 6.66 55.6 30.1 7.27
67 59.3 43.4 5.47 56.5 42.3 5.98 53.5 41.2 6.53 50.5 40.0 7.12
63†† 55.0 42.0 5.40 52.4 40.9 5.89 49.6 39.7 6.43 46.8 38.5 7.01
62 54.4 52.8 5.39 51.9 51.4 5.88 49.6 49.6 6.43 47.2 47.2 7.02
57 53.9 53.9 5.38 51.7 51.7 5.88 49.5 49.5 6.43 47.2 47.2 7.02
2200
72 64.9 34.0 5.66 62.4 33.3 6.19 59.4 32.4 6.77 56.0 31.2 7.38
67 59.9 45.3 5.58 57.0 44.3 6.09 53.9 43.1 6.65 50.9 41.9 7.23
63†† 55.5 43.9 5.51 52.8 42.7 6.00 50.0 41.5 6.54 47.2 40.3 7.12
62 55.2 55.0 5.50 52.9 52.9 6.01 50.6 50.6 6.56 48.2 48.2 7.16
57 55.1 55.1 5.50 52.9 52.9 6.01 50.6 50.6 6.56 48.2 48.2 7.16
Multipliers for Determining the Performance With Other Indoor Sections
Indoor
Section Size
Cooling
Indoor
Section Size
Cooling
Capacity Power Capacity Power
FB4AN(A,F,M)
060 1.00 1.00
FG3AAA
060 0.99 0.96
FB5AN(A,F)
060 1.00 1.00
CC5A/CD5AA
060 0.97 0.95
FB4AN(F,M,B)
070 1.03 0.98
CC5A/CD5AW
060 0.99 0.96
F(A,B)4AN(F,B)
060 1.00 1.00
CD3(A,B)A
060 0.97 0.95
FK4ANF
006 1.02 0.98
CE3AA
060 1.01 0.96
FC4BN(F,B)
060 1.00 1.00