3
 
CERTIFICATION APPLIES ONLY WHEN THE 
COMPLETE SYSTEM IS LISTED WITH ARI.
 
Physical data
 
NOTE:
 
 See unit Installation Instructions for proper installation.
* Tube sizes are for runs up to 50 ft.
For tube set over 50 ft, consult Long-Line Application Guideline.
 
METERING DEVICE
 
* Chatleff-type piston on -30 series units. AccuRater
 
 
 type on -31
series units.
† Piston shipped with outdoor unit and must be installed in approved
indoor coil.
 
MODEL 38YKB 018-30/31 024-30/31 030-30/31 036-30/31 042-30/31 048-30/31 060-30/31
OPER. WEIGHT (lb)
 
139 142 183 206 216 266 293
 
COMPRESSOR MFR.
 
Copeland Scroll/
Tecumseh Recip
Copeland Scroll
 
REFRIGERANT
 
22
 
Control
 
Piston
 
Charge (lb)
 
3.76/4.13 3.76 4.88 6.38 8.01 11.51 12.38
 
CONDENSER FAN
Air Discharge
 
Vertical
 
Air Qty (Cfm)
 
1900 2400 2900 3100
 
Motor Rpm (60 Hz)
 
1075 825 1100
 
CONDENSER COIL
Face Area (sq. ft)
 
8.75 12.12 15.15 12.12 15.15 18.18
 
CONNECTION (in. ID)
 
Sweat
 
Vapor
 
5/8 3/4 7/8
 
Liquid
 
3/8
 
REFRIGERANT TUBES* 
(in. OD)
Vapor
 
5/8 3/4 7/8 1-1/8
 
Liquid
 
3/8
 
SIZE SERIES
OUTDOOR 
PISTON*
INDOOR 
PISTON†
018
 
30, 31 42 55
 
024
 
30, 31 49 61
 
030
 
30, 31 59 70
 
036
 
30, 31 61 78
 
042
 
30, 31 63 82
 
048
 
30, 31 70 88
 
060
 
30, 31 78 98