12
AIR THROW DATA
Unit Size
Approximate Air Throw ft. (m)
Low Medium High Turbo
9K 18 (5.5) 20 (6.1) 23 (7.0) NA
12 K 19 (5.8) 21 (6.4) 25 (7.6) NA
18 K 25 (7.6) 30 (9.1) 32 (9.8) 35 (10.7)
24 K 23 (7.0) 27 (8.2) 30 (9.1) 37 (11.3)
SOUND RATINGS
Outdoor Units
Model Number Sound Power dBA Sound Pressure dBA
3 8 G X C 0 0 9 --- --- --- 1 66 53
3 8 G X C 0 1 2 --- --- --- 1 66 55
3 8 G X C 0 1 8 --- --- --- 3 67 56
3 8 G X C 0 2 4 --- --- --- 3 66 55
3 8 G X Q 0 0 9 --- --- --- 1 ( c o o l / h e a t ) 65/66 54/55
3 8 G X Q 0 1 2 --- --- --- 1 ( c o o l / h e a t ) 65/66 54/55
3 8 G X Q 0 1 8 --- --- --- 3 ( c o o l / h e a t ) 67/66 56/55
3 8 G X Q 0 2 4 --- --- --- 3 ( c o o l / h e a t ) 68/69 57/58
Indoor Units
Model Number
Low Medium High Turbo
Sound
Power dBA
Sound
Pressure
dBA
Sound
Power dBA
Sound
Pressure
dBA
Sound
Power dBA
Sound
Pressure
dBA
Sound
Power dBA
Sound
Pressure
dBA
4 0 G X C 0 0 9 --- --- --- 1 42 31 47 36 51 40 --- ---
4 0 G X C 0 1 2 --- --- --- 1 44 33 46 35 48 37 --- ---
4 0 G X C 0 1 8 --- --- --- 3 52 41 55 44 57 46 60 49
4 0 G X C 0 2 4 --- --- --- 3 48 37 51 40 54 43 62 51
4 0 G X Q 0 0 9 --- --- --- 1
(cool/heat)
42/42 31/31 47/44 36/33 51/49 40/38 --- ---
4 0 G X Q 0 1 2 --- --- --- 1
(cool/heat)
44/43 33/32 46/45 35/34 48/47 37/36 --- ---
4 0 G X Q 0 1 8 --- --- --- 3
(cool/heat)
52/48 41/37 55/52 44/41 57/55 46/44 60/59 49/48
4 0 G X Q 0 2 4 --- --- --- 3
(cool/heat)
48/50 37/39 51/51 40/40 54/54 43/43 62/61 51/50
NOTES:
1. Sound power ratings are per ARI 270 and ARI 350
2. Sound pressure ratings are estimated sound pressure, 3 feet (.91 m) from the unit, based on sound power data.
ELECTRICAL DATA
UNIT
SIZE
SYSTEM
VOLTAGE
OPERATING
VOLTAGE*
COMPRESSOR
OUTDOOR FAN INDOOR FAN{
MCA
MAX
FUSE/CB
AMP
V O LT --- P H --- H Z MAX/MIN RLA LRA FLA HP W VOLTS FLA HP W
9K 11 5 --- 1 --- 6 0 127/104 4.0 33 0.6 0.04 30 115 0.3 0.027 30 20 25
12 K 1 1 5 --- 1 --- 6 0 127/104 4.0 33 0.6 0.04 30 115 0.45 0.027 20 20 25
18 K 208/ 230 --- 1 --- 60 253/187 7.46 41 0.65 0.082 60 208/230 0.24 0.027 20 14 25
24 K 208/ 230 --- 1 --- 60 253/187 8.4 41 0.65 0.082 60 208/230 0.38 0.041 35 16 30
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ Indoor fan powered from outdoor unit.
LEGEND
FLA --- Fu l l L o a d A m p s
LRA --- L o c k e d Ro t o r A m p s
MCA --- Minimum Circuit Amps
RLA --- RatedLoadAmps
38/40GXC(Q)