EasyManua.ls Logo

Carrier 40MAQ Series - Heating Performance

Carrier 40MAQ Series
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20
HEATING PERFORMANCE
Model
Heating Outdoor conditions (DB)
Indoor Conditions DB 53.6F(12C) 44.6F(7C) 39.2F(4C) 32F(0C) 24.8F(-4C) 19.4F(-7C) 17F(-8C) 5F(-15C)
09(115V)
59F(15C)
TH 11.2 11.1 10.89 10.65 9.87 9.11 8.27 6.71
Input 0.73 0.79 1.04 1.01 0.96 0.9 0.84 0.8
64.4F(18C)
TH 11.1 10.8 10.65 10.54 9.63 8.84 8.01 5.46
Input 0.78 0.8 1.08 1.03 0.98 0.94 0.9 0.82
69F(20.5C)
TH 10.8 10.6 10.48 10.32 9.43 8.55 7.95 4.29
Input 0.8 0.81 1.11 1.05 1 0.98 0.96 0.84
71.6F(22C)
TH 10.6 10.3 10.21 10.11 9.23 8.41 7.89 4.11
Input 0.82 0.83 1.15 1.07 1.02 1.02 0.92 0.86
12(115V)
59F(15C)
TH 11.8 12.7 12.42 11.32 10.4 9.54 8.9 5.75
Input 0.79 1.01 1.05 1.1 1.02 1 0.98 0.83
64.4F(18C)
TH 12.1 12.7 12.32 11.34 10.32 9.32 8.81 6.14
Input 0.83 1.37 1.4 1.26 1.22 1.27 1.01 0.91
69F(20.5C)
TH 12.3 12.6 12.12 11.32 10.21 9.12 8.43 6.49
Input 0.83 1.1 1.12 1.19 1.19 1.25 1.03 0.98
71.6F(22C)
TH 11.1 12.4 12.01 11.21 10.01 9.02 8.21 6.01
Input 0.85 1.15 1.16 1.21 1.23 1.31 1.05 1
09
(208-230V)
59F(15C) TH 11.2 11.1 10.89 10.65 9.87 9.11 8.27 6.71
Input 0.73 0.79 1.04 1.01 0.96 0.9 0.84 0.8
64.4F(18C)
TH 11.1 10.8 10.65 10.54 9.63 8.84 8.01 5.46
Input 0.78 0.8 1.08 1.03 0.98 0.94 0.9 0.82
69F(20.5C)
TH 10.8 10.6 10.48 10.32 9.43 8.55 7.95 4.29
Input 0.8 0.81 1.11 1.05 1 0.98 0.96 0.84
71.6F(22C)
TH 10.6 10.3 10.21 10.11 9.23 8.41 7.89 4.11
Input 0.82 0.83 1.15 1.07 1.02 1.02 0.92 0.86
12
(208-230V)
59F(15C) TH 11.8 12.7 12.42 11.32 10.4 9.54 8.9 5.75
Input 0.79 1.01 1.05 1.1 1.02 1 0.98 0.83
64.4F(18C) TH 12.1 12.7 12.32 11.34 10.32 9.32 8.81 6.14
Input 0.83 1.37 1.4 1.26 1.22 1.27 1.01 0.91
69F(20.5C) TH 12.3 12.6 12.12 11.32 10.21 9.12 8.43 6.49
Input 0.83 1.1 1.12 1.19 1.19 1.25 1.03 0.98
71.6F(22C) TH 11.1 12.4 12.01 11.21 10.01 9.02 8.21 6.01
Input 0.85 1.15 1.16 1.21 1.23 1.31 1.05 1
18
(208-230V)
59F(15C) TH 23.2 20.5 19.42 17.56 16.52 14.28 12.08 9.39
Input 1.58 1.49 1.48 1.58 1.46 1.4 1.35 1.21
64.4F(18C) TH 22.4 20.1 18.66 16.89 16.05 13.94 12.06 9.16
Input 1.62 1.55 1.55 1.61 1.52 1.45 1.4 1.29
69F(20.5C) TH 21.7 19.7 17.93 16.26 15.62 13.62 12.07 8.95
Input 1.67 1.62 1.63 1.65 1.58 1.5 1.45 1.38
71.6F(22C) TH 21 19 17.23 15.56 14.92 12.92 11.37 8.25
Input 1.72 1.67 1.68 1.7 1.63 1.55 1.5 1.43
24
(208-230V)
59F(15C) TH 28.6 27.8 25.85 23.56 23.42 23.22 23.16 18.93
Input 2 2.25 2.24 2.21 2.2 2.23 2.24 2.17
64.4F(18C)
TH 27.6 27.6 24.52 23.54 23.4 22.52 20.45 17.45
Input 2.24 2.45 2.35 2.35 2.32 2.23 2.21 2.16
69F(20.5C)
TH 29.1 29.3 26.75 24.63 22.98 21.85 19.61 16.38
Input 2.39 2.74 2.64 2.58 2.42 2.25 2.2 2.18
71.6F(22C)
TH 26.9 27.5 24.21 23.41 22.54 21.67 19.54 16.24
Input 2 2.25 2.24 2.21 2.2 2.23 2.24 2.17
30
(208-230V)
59F(15C)
TH 43 41.2 37.52 34.65 32.32 30.65 28.84 20.51
Input 3.79 3.99 3.69 3.43 3.2 2.96 2.82 2.61
64.4F(18C)
TH 39.6 39.9 36.55 33.84 30.95 28.58 26.47 19.96
Input 3.35 4.23 3.85 3.65 3.24 3.11 3.04 2.76
69F(20.5C)
TH 36.3 38.6 35.62 33.07 29.62 26.54 24.13 19.43
Input 3.45 4.46 4.01 3.9 3.31 3.2 3.16 2.89
71.6F(22C)
TH 32.9 35.2 32.22 29.67 26.22 23.14 20.73 16.03
Input 3.68 4.69 4.24 4.13 3.54 3.43 3.39 3.12
LEGEND
DB - Dry Bulb
WB - Wet Bulb
TH - Total Net Heating Capacity (1000 Btu/hour)
Input - Total Power (kW)