6 --- IPM malfunction or IGBT over ---strong current protection --- diagnosis and solution (P0)
Error Code P0
Malfunction conditions
When the voltage signal that IPM sends to compressor drive chip is abnormal, the display LED will
shows P0” and the system will turn off.
Possible Causes
Wiring mistake
IPM malfunction
Defective outdoor fan assembly
Compressor malfunction; Outdoor PCB faulty
Trouble shooting:
Is the wiring between main PCB
and compressor connected incorrectly?
Are wires and connectors broken?
Correct the connection or replace
the wires and connectors.
Yes
No
IPM continuity check. Check if the
IPM terminal resistance values are
uniform.
Replace the IPM board or replace the
main PCB if the IPM board and main
PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
Refer to the Notes below, check whether the
resistance of the fan motor is normal. If not, replace
the fan motor.
Yes
Check if the compressor resistance
values are uniform .
No Replace the compressor.
Yes
Replace the outdoor main PCB if the
main PCB and IPM are separate.
A14486
Note:
Measure the black p in and red pin of the motor terminals, the resistance should be around the value specified below:
Model size
Voltage
Resistance Value at
68_F(20_FC)
9K and 12K 115 50
12K
208-230
293
18K AC / 17K HP 84.5
22K 88.5