Is the wiring between main PCB
and compressor connected incorrectly?
Are wires and connectors broken?
Correct the connection or replace
the wires and connectors.
Yes
No
IPM continuity check. Check if the
IPM terminal resistance values are
uniform.
Replace the IPM board or replace the
main PCB if the IPM board and main
PCB are integrated together.
No
Check if the outdoor fan runs
properly or the outdoor unit
ventilation is good.
Yes
No
Refer to the Notes below, check whether the
resistance of the fan motor is normal. If not, replace
the fan motor.
Yes
Check if the compressor resistance
values are uniform .
No Replace the compressor.
Yes
Replace the outdoor main PCB if the
main PCB and IPM are separate.