Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 18-40VMM001-02 Printed in U.S.A. Form 40VMM-2SI Pg 1 1-18 Replaces: 40VMM-1SI
Installation and Maintenance Instructions
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . .1,2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-19
Step 1 — Unpack and Inspect Units . . . . . . . . . . . 11
PROTECTING UNITS FROM DAMAGE
PREPARING JOBSITE FOR UNIT INSTALLATION
IDENTIFYING AND PREPARING UNITS
Step 2 — Position the Unit . . . . . . . . . . . . . . . . . . . 11
Step 3 — Mount the Unit . . . . . . . . . . . . . . . . . . . . . 11
INSTALLING HANGER BOLTS
MOUNTING UNIT
INSTALLING DUCT
RETURN AIR ARRANGEMENT
Step 4 — Connect Piping. . . . . . . . . . . . . . . . . . . . . 13
CONDENSATE PIPING
REFRIGERANT PIPING
Step 5 — Complete Electrical Connections. . . . . 14
Step 6 — Position and Connect Controller . . . . . 16
CONTROL WIRING
OPTION/EXTENSIONS OF COMMUNICATION
WIRING
ACB Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20, 20
Pre-Start Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Drain Pump and Drainage Test . . . . . . . . . . . . . . . 20
System Operation Check . . . . . . . . . . . . . . . . . . . . 20
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
INDOOR UNIT ADDRESSING . . . . . . . . . . . . . 21, 21
Wireless Remote Controller (40VM900001) . . . . . 21
Non-Programmable Controller (40VM900002). . . 21
Programmable Controller (40VM900003). . . . . . . 22
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . 23-23
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . 24
APPENDIX A — DIP SWITCH SETTINGS . . . . . . . . 25
SAFETY CONSIDERATIONS
Improper installation, adjustment, alteration, service,
maintenance, or use can cause explosion, fire, electrical shock,
or other conditions which may cause death, personal injury or
property damage. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this
product.
Follow all safety codes. Wear safety glasses, protective
clothing, and work gloves. Use quenching cloth for brazing
operations. Have fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local
building codes and the current editions of the National
Electrical Code (NEC) ANSI/NFPA (American National
Standards Institute/National Fire Protection Association) 70. In
Canada, refer to the current editions of the Canadian Electrical
Code CSA (Canadian Standards Association) C22.1.
Understand the signal words — DANGER, WARNING,
and CAUTION. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies hazards that could result in personal
injury or death. CAUTION is used to identify unsafe practices,
which would result in minor personal injury or product and
property damage.
Recognize safety information. This is the safety-alert
symbol ( ). When this symbol is displayed on the unit and in
instructions or manuals, be alert to the potential for personal
injury. Installing, starting up, and servicing equipment can be
hazardous due to system pressure, electrical components, and
equipment location.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all
disconnect locations to alert others not to restore power
until work is completed.
WARNING
When installing the equipment in a small space, provide
adequate measures to avoid refrigerant concentration
exceeding safety limits due to refrigerant leak. In case of
refrigerant leak during installation, ventilate the space
immediately. Failure to follow this procedure may lead to
personal injury.
WARNING
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and
goggles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from
system using high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and work area should be well ventilated. Refrigerant
in contact with an open flame produces toxic gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch
any oil that may come out of the lines and as a gage
for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when
necessary. Oil can ignite when exposed to torch
flame.
Failure to follow these procedures may result in personal
injury or death.
40VMM007A-048A
Medium Static Duct Indoor Unit for
Variable Refrigerant Flow (VRF) Systems

Questions and Answers

  • J
    James SmithAug 15, 2025
    What to do if there is a communication error between indoor and outdoor unit of Carrier 40VMM?
    • R
      Rebecca MooreAug 15, 2025
      If you're experiencing a communication error between the indoor and outdoor units of your Carrier Air Conditioner, the signal wires might be short-circuited, disconnected, or too close to an electromagnetic source. First, check and reconnect the signal wire, ensuring it's properly connected. If the issue persists, try distancing the signal wires from any electromagnetic sources. If neither of these steps resolves the problem, the PC board may be faulty and require replacement.
  • J
    Jimmy CruzAug 18, 2025
    What to do if Carrier 40VMM Air Conditioner shows communication error between indoor unit and controller?
    • S
      samuel11Aug 18, 2025
      If your Carrier Air Conditioner shows a communication error between the indoor unit and the controller, the signal wires are likely the issue. Begin by checking and reconnecting any short-circuited or disconnected signal wires. If the problem continues, ensure the signal wires are not near any electromagnetic sources; if they are, distance them. If the problem persists, the PC board might be faulty and needs replacing.
  • B
    bryan40Aug 21, 2025
    Why does my Carrier 40VMM Air Conditioner have a heating/cooling mode conflict?
    • D
      Douglas BennettAug 22, 2025
      The Carrier Air Conditioner system may be experiencing a conflict if one unit is sending a heating signal while the system is in cooling or fan-only mode, or vice versa. To resolve this, ensure all units are set to the same mode. If the system should be cooling, make sure all units are in cooling mode. If heating is required, ensure all units are set to heating mode.
  • C
    carly39Aug 25, 2025
    How to check temperature sensor on Carrier Air Conditioner?
    • C
      Christopher RoachAug 26, 2025
      If you are getting a temperature sensor error on your Carrier Air Conditioner, it could be due to a loose connection, a short-circuited sensor, or a faulty PC board. Start by tightening the connection at the port on the PC board. If that doesn't work, use a multimeter to measure the resistance of the sensor; if it's £ 100 ohms, replace the sensor. If neither of these steps resolves the issue, the PC board may need to be replaced.
  • P
    Paul EwingAug 28, 2025
    What to do if my Carrier 40VMM shows a condensate error?
    • D
      dennis50Aug 28, 2025
      If you're encountering a condensate error with your Carrier Air Conditioner, several factors could be the cause. First, check for loose or disconnected connections and tighten or reconnect them at the port on the PC board. Also, inspect the slope to ensure the water level float is not stuck. Furthermore, verify that the trap slope isn't too steep and adjust it if necessary. Check the drain pipe length and adjust if it's too long. Finally, the drain pump might be faulty, requiring replacement.
  • R
    Rose MurphyAug 31, 2025
    What causes DC fan motor issues in Carrier 40VMM?
    • L
      lucas29Aug 31, 2025
      If you're experiencing issues with the DC fan motor in your Carrier Air Conditioner, it could be due to several reasons. The motor might be operating beyond its limits, indicating a need to check and correct the external static pressure on the unit. Alternatively, the DC motor itself could be faulty and require replacement. Lastly, a faulty PC board could also be the cause, necessitating its replacement.
  • J
    Julie GillespieSep 3, 2025
    What causes an EEV error in Carrier 40VMM?
    • S
      Sarah MillerSep 3, 2025
      If your Carrier Air Conditioner is displaying an EEV error, the EEV wires might be short-circuited or disconnected, or the EEV itself might be stopped. Begin by replacing the EEV wires. If the issue persists, replace the EEV. If neither of these steps resolves the problem, the PC board may be faulty and require replacement.
  • A
    Anthony FischerSep 7, 2025
    What to do if Carrier 40VMM Air Conditioner shows 'No Address' when powered on for the first time?
    • M
      Melinda SmithSep 7, 2025
      If your Carrier Air Conditioner shows 'No Address' when powered on for the first time, it means the indoor unit lacks an address. You can resolve this by running the automatic addressing option at the outdoor unit. Alternatively, use a remote wireless or wired controller to readdress the indoor unit.
  • B
    Brooke RaySep 12, 2025
    What does EEPROM error mean on Carrier Air Conditioner?
    • J
      Jonathan HallSep 12, 2025
      If your Carrier Air Conditioner is showing an EEPROM error, it indicates a fault with the chip or PC board. In this case, the solution is to replace the PC board.

Summary

Safety Considerations

General Safety and Signal Word Definitions

Defines signal words (DANGER, WARNING, CAUTION) and safety alert symbol for hazard recognition.

Installation Safety Warnings

Covers critical safety warnings for electrical shock, refrigerant leaks, and component handling.

Installation Procedures

Piping Connections

Detailed steps for connecting condensate and refrigerant piping.

Electrical Connections and Wiring

Guidance on making electrical connections, grounding, and wiring requirements.

Refrigerant Piping Safety and Best Practices

Safety precautions and procedures for handling and installing refrigerant piping.

Start-Up and System Checks

Indoor Unit Addressing

Troubleshooting and Error Codes

Specific Error Code Resolution

Detailed causes and solutions for specific error codes like E1, E2, E9, FE, etc.

Troubleshooting Common Problems

A table detailing common problems, their causes, and proposed solutions.

Carrier 40VMM Series Specifications

General IconGeneral
BrandCarrier
Model40VMM Series
CategoryAir Conditioner
LanguageEnglish