22
3. While the system is in operation, check the following on
the outdoor unit:
a. No abnormal vibration or noise is noticed.
b. Condenser fan is in operation.
c. Indicator light is showing normal operation and no
error is indicated.
NOTE:  If the  unit  is  turned  off or  restarted,  there  is a time
delay of three minutes for the compressor to start from the time
the power is restored.
MAINTENANCE
EVERY 3 MONTHS:
• Check  the  air  filter  condition.  Clean  or  replace  if
necessary.
EVERY 6 MONTHS:
Follow the 3-month maintenance schedule. In addition:
• Clean condensate tray with suitable cleaning agent.
• Clean the grille and panel if applicable.
EVERY 12 MONTHS:
Follow the 6-month maintenance schedule. In addition:
• Be sure all electrical connections are secure.
• Check condensate pump operation if applicable.
• Check the heating and cooling action to confirm proper
operation.
INDOOR UNIT ADDRESSING
For  proper  system  operation,  each  indoor  unit  must  have  a
unique address set from 0 to 63. When setting an address by
remote  controller,  the  outdoor  units,  indoor  units,  and  MDC
must be powered on. If FE is displayed on the LED screen or
display board, this unit has no address. After setting all indoor
unit addresses, turn off the power supply to all indoor units to
clear the errors.
Indoor unit addressing can be distributed automatically in the
heat pump system. When dip switch “S6” on the outdoor unit’s
main  PCB  board is  set  to 00  (default  set  in  factory),  indoor
units  are  set  for auto-addressing. When  powering  on  for  the
first time, it takes six minutes or more to finish auto-addressing
each indoor unit. The heat recovery system cannot accomplish
this function at this time.
Wireless Remote Controller (40VM900001)  — 
Indoor  unit  addressing  can  be  performed  using  the  wireless
remote controller. When using the wireless controller, the user
must maintain a line of sight with the receiver on the indoor
unit. See Fig. 35 for a description of the buttons on the wireless
remote.
Fig. 35 —Wireless Remote Controller 
(40VM900001)
4. Use a tool to press and hold the LOCK button for at least
ten seconds. 
5. Press        to activate. 
6. Click        or         to select an address and press        to send
the setting.
To display an indoor unit address, use a tool to press and hold
the LOCK button for at least ten seconds, and press         to
query the addresses.
Non-Programmable Controller
When setting an address, connect only one wired controller to 
an indoor unit.
Press ROOM  TEMP and SWING  simultaneously  for three
seconds. If there is no address for this indoor unit, the display
shows FE# 00. See Fig. 36. Otherwise, the display shows the
current address of the indoor unit.
Fig. 36 —Non-Programmable Controller IDU 
Addressing Menu
CAUTION
When  servicing  or  repairing  this  unit,  use  only  factory-
approved  service  replacement  parts.  Refer  to  the  rating
plate  on  the  unit  for  complete  unit  model  number,  serial
number, and company address. Any substitution of parts or
controls not approved by the factory will be at the owner’s
risk and may result in equipment damage.
CAUTION
To avoid equipment damage, do not attempt to reuse any
mechanical  or  electrical  controllers  that  have  been  wet.
Replace defective controller.
RESET
TIMER ON
TIMER OFF
SWING
AIR DIRECTION
CLOCK
OK
SWING
MODE
FAN
AUTO
COOL
DRY
HEAT
FAN
TEMP
SET
CLOCK
SET
HOUR
FAN SPEED
LOCK
C/H
6 – AIR DIRECTION
2 – FAN SPEED SETTING
4 – ADJUST UP
9 – CLOCK SETTING
10 – TIMER ON
14 – OK (CONFIRM)
11 – TIMER OFF
1 – MODE SETTING
5 – ON/OFF
3 – ADJUST DOWN
7 – AIR VERT. SWING
8 – AIR HORIZ. SWING
12 – RESET
13 – LOCK
15 – COOL/HEAT
A40-1734
MODE
FAN TEMP. DOWN
OK
TEMP. UP ON/OFF
TIMER
ROOM TEMP.
SWING
#