25
Table 6 —
 Troubleshooting
Replacement Parts
Quote  the  unit  model  number  and  unit  serial  number  when
ordering replacement parts or contacting the factory about the
unit. This information can be found on the serial plate attached
to the unit. See Fig. 41.
ERROR DESCRIPTION POSSIBLE CAUSES POSSIBLE SOLUTIONS
DD Heating / Cooling Mode Conflict
System is in cooling or fan only mode and 
heating signal is received from a unit on the 
system.
All units should be in cooling mode for system to 
stay in cooling mode.
System is in heating mode and cooling 
signal is received from a unit in the system.
All units should be in heating mode.
E1
Communication Error Between 
Indoor & Outdoor Unit
Signal wires are short-circuited or 
disconnected.
Check or reconnect signal wire.
Signal wire close to electromagnetic 
source.
Distance signal wires from electromagnetic 
source.
PC board fault. Replace PC board.
E2, E4, 
E5
Check Temperature Sensor
Loose connection at port on PC board. Tighten the connection at port on PC board.
Sensor is short-circuited. Using multi-meter, measure resistance of the 
sensor. If the resistance is £ 100 ohms, change 
the sensor.
PC board fault. Replace PC board.
E6 DC Fan Motor
Operating beyond limits. Check and correct external static pressure on the 
unit.
DC motor fault. Replace DC motor.
PC board fault. Replace PC board.
E7 EEPROM Error (Data Storage) Chip or PC board fault. Replace PC board.
E9
Communication Error Between 
Indoor Unit and Controller
Signal wires are short-circuited or 
disconnected.
Check or reconnect signal wires.
Signal wires close to electromagnetic 
source.
Distance signal wires from electromagnetic 
source.
PC board fault. Replace PC board.
EB EEV Error
EEV wires are short-circuited or 
disconnected.
Replace EEV wires.
EEV stop. Replace EEV.
PC board fault. Replace PC board.
ED Outdoor Unit Error Outdoor unit fault. Refer to outdoor unit troubleshooting guide.
EE Condensate Error
Loose connection or disconnected. Tighten the connection or reconnect at port on 
PC board.
Water level float is stuck. Inspect the slope.
Trap slope is too steep. Adjust the trap slope.
Drain pipe is too long. Adjust the length of drain pipe.
Drain pump faulty. Replace the drain pump.
FE
No Address When Power ON for first 
time
Indoor unit without address.
Run automatic addressing option at the outdoor 
unit.
Use remote wireless or wired controller to 
readdress indoor unit.
UU MDC Auto System-Check Mode MDC fault Refer to MDC troubleshooting guide.
LEGEND
EEV — Electronic Expansion Valve
EEPROM — Electronically Erasable Programmable Read-only Memory
MDC — Multiport Distribution Controller
PC — Process Controller