•  Disconnect the power supply to the unit before carrying 
out any work on a unit.
•  Disconnect the actuator power supply cable.
  -  230 V type actuator used with the Carrier 
numeric controller: Disconnect the actuator 
power supply cable tted with a quick connector.
  -  230 V actuator used with an electronic 
thermostat: Remove the plastic protection cover 
held in place with two screws. Disconnect the 
actuator power supply cable connected to the 
quick connector. This can be done by pressing 
down the spring tongue using a screwdriver and 
pulling out the wire from the appropriate terminal.
•  Uncouple the faulty actuator. Retting is by the reversal 
of the procedure described above.
WARNING: Ensure that the actuator is rmly screwed to 
the valve body (maximum torque 15 N·m).
4.6.4 - Valve body replacement procedure
•   Disconnect the power supply before carrying out any 
work on a unit.
•  Close the isolating valves on the manifolds.
•   Unscrew the union nuts to disconnect the exible water 
pipes.
•   Remove the valve actuators taking care to identify the 
cooling and heating valves.
•   Disconnect the exible condensate drain pipe which is 
held in place by a collar (the collar is not supplied by 
Carrier).
•   Remove the two-way or four-way water ow control 
valve bodies. Depending how the unit is congured, 
the four-way valve coupling may be tted with a 
heating/cooling changeover switch, if so do not 
remove it.
•   Fit the new valve body to the coil (t new gaskets).
•   Reconnect the exible condensate drain pipe which is 
held in place by a collar (the collar is not supplied by 
Carrier).
•   Ret the valve actuators taking care to ensure that 
they are correctly xed to the valve body.
•   Reconnect the exible water pipes by tightening the 
union nuts. Retighten all the water connections and 
ensure that all gaskets have been changed and correctly 
tted (maximum torque 15 N·m).
•   Open the isolating valves on the manifolds and purge 
all air from the system.
•  Check that there are no leaks and reconnect the power 
to the unit.
WARNING: When replacing a valve always ensure that 
the direction of ow through the valve is as shown by the 
arrow on the valve body. If the direction of ow is wrong, 
the valve body will deteriorate rapidly.
Minimum bending radius: 
•  non-insulated pipes 72 mm
•  insulated pipes 106 mm.
electric heater 
WARNING: Disconnect the power supply before carrying 
out any work on the unit.
If the electric heater develops a fault, it must be replaced; 
this requires the removal of the fan motor assembly: Fig. 17 
(17a = screw).
CAUTION: Do not touch the live metal heater elements 
when the electric heater is connected to the power supply.
Electric heater replacement procedure:
•  Remove the lter.
•   Remove the fan motor assembly access panel.
•   Identify and note the fan speeds wired to the auto-
transformer terminal block. Disconnect the power 
supply cable.
•   Remove the fan motor assembly.
  NOTE: Be careful not to touch the fan blades during 
the removal process to avoid unbalancing the fans.
•  Disconnect the electric heater power supply cables 
and remove them through the cable conduit.
•  Unscrew the defective heater(s) and replace it (them).
•   Replacement of the fan motor assembly is by the 
reversal of the above procedure.
WARNING : Carrier Electronic thermostat type B and D 
are embedded with Electric heater relay 8 Amps. 
Accordingly, Carrier requires an additional protection 
relay for electric heater 2000W and 3200W.
WARNING : In case of customer supplied controller, 
Carrier recommends to set up an additional protection 
relay corresponding to the electric heater capacity.
According to the g. 26, the condensate pump installation 
require the following actions:
•      Press the pump at the lowest position according to the 
available height in the false celling (g. 26b)
•      Check the sealing of the hydraulic connection of the 
condensate pump and condensate recovery
The meaning of the electrical wires is described below:
•      Brown - Blue wires : Electrical supply 230V 50/60Hz
•      Black - Grey wires : Alarm contact Normally Closed 
(NC) 250V/8A maxi