EasyManua.ls Logo

Carrier 42LUVH045N - Installation Procedures and Details; Wrench Torque for Installation; Cable Connection Guidelines; Pipe Length and Elevation Limits

Carrier 42LUVH045N
43 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
6. Installation details
6.1 Wrench torque sheet for installation
Outside diameter
Torque
mm
inch
Kgf.m
Ф6.35
1/4
1.8
Ф9.52
3/8
4.2
Ф12.7
1/2
5.5
6.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Grade
Unit
9K
12K
18K
mm
2
1.5
1.5
2.5
6.3 Pipe length and the elevation
Capacity
Btu/h
Pipe size
Standard
length
(m)
Min.
length
(m)
Max.
Elevation
B (m)
Max.
Length
A (m)
Additional
refrigerant
(g/m)
Gas
Liquid
9K~18K
3/8’’ (Ф9.52)
1/4’’
(Ф6.35)
5
3
8
20
20
1/2’’ (Ф12.7)
1/4’’
(Ф6.35)
5
3
8
20
20

Related product manuals