If the machine runs in rating capacity test mode, indoor fan runs with rating speed, and anti-cold-wind is
disabled.
8.7.2 Indoor fan speed can be set as high, medium, low or auto grade, but anti-cold-wind function is
preferential.
Auto fan action in heating mode.
After 7minutes start the operation frequency of compressor submits to following rule :
1)When the machine runs, if ΔTh stays in a zone for 3 minutes, action of frequency is as follow:
Zone A: Elevate current frequency one grade, and not stop until the maximum grade.
Zone B: Elevate or keep or descend current frequency.
Zone H: Compressor stops after running with F1 for 60 minutes or when ΔTh>6℃.
2)Temperature difference (ΔTcon) choice.
After power on, the machine will self-diagnose, and if there are no J1 and J2 jump wires, ΔTcon
will be set as 0℃.
Remark: ΔTcon can be changed among 0, -2,- 4℃, the
default is 0℃
.