Loading...
Ta (˚C)
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
Tsc
–0.5
HH
(HH)
H+ (HH)
H (HH)
L+ (H+)
L (H)
L (H)
L (L+)
D
C
B
A
E
F
G
No.
4
Item
Air speed selection
Outline of specifications
1) Operation with (HH), (H), (L) or [AUTO] mode is carried
out by the command from the remote controller.
2) When the air speed mode [AUTO] is selected, the air
speed varies by the difference between Ta and Ts.
<COOL>
Controlling operation in case when thermo of remote
controller works is same as a case when thermo of the
body works.
If the air speed has been changed once, it is not changed
for 3 minutes. However when the air volume is exchanged,
the air speed changes.
When cooling operation has started, select a downward
slope for the air speed, that is, the high position.
If the temperature is just on the difference boundary, the
air speed does not change.
Mode in the parentheses indicates one in automatic
cooling operation.
Remarks
HH > H+ > H > L+ >
L > UL