No.
4
Item
Air speed
selection
(Continued):
Outline of specifications
Remarks
Selection of high
ceiling type
CODE No.:
[5d] or selection of
high ceiling on P.C.
board SW501
However only when
Tcj:
Indoor heat exchanger
sensor temperature
the high ceiling
selection is set to
[Standard]
CODE No.
[5d]
SW501 (1)/(2)
Tap
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
FB
FC
FD
Standard Type 1 Type 3
013
OFF/OFF ON/OFF OFF/ON
COOL COOL COOL
HH
HH
H+
H+, H
H
L+
H+ L
H
L
L+
L
UL UL UL
L+
SVM-13050.indb 29SVM-13050.indb 29 6/27/13 10:35 AM6/27/13 10:35 AM
(˚C)
F4F5
F5
47
42
3) In automatic cooling the revolution frequency of (HH) is
set larger than that in the standard cooling operation.
4) Self-clean operation
When performing self-clean operation after stopping the
cooling operation, the mode becomes [UL].
Tc
Tcj
[Self-clean
] is
displayed.
HH
0131CP 0181CP 0241CP 0251CP 0301CP 0361CP 0401CP 0481CP 0601CP
F1 1000 1100 1140 1140 1140 1140 1140 1140 1140
F2 830 880 1080 1080 1080 1080 1080 1080 1120
F3 800 850 990 990 990 990 1000 1020 1100
F4 790 830 990 990 990 990 1000 1000 1080
F5 780 820 990 990 990 990 990 990 1040
F6 780 790 910 910 910 910 990 990 1040
F7 690 710 790 790 790 790 810 860 1000
F8 670 700 790 790 790 790 790 840 900
F9 660 690 700 700 700 700 780 830 880
FA 590 590 660 660 660 660 710 740 780
FB 550 550 600 600 600 600 660 680 760
FC 550 550 550 550 550 550 640 670 740
FD 350 350 350 350 350 350 350 350 350
Tap
Revolution speed (rpm)
* When the factory is shipped, self-clean operation is set.