HA control 1) This control is connected to telecontrol system or remote
start/stop I/F, etc, and start/stop are available by HA signal
input from the remote position.
2) This control outputs start/stop status to HA output terminal.
3) I/O specifications conform to JEMA regulations.
4)
This control outputs [Operation OFF (STOP) signal] to HA
output terminal while self-cleaning operation. However selection
of [Operation ON (Operating) signal] is possible by changing
[0000 (At shipment)] of CODE No. (DN) [CC] to [0001]. In this
case, if HA is input during self-clean operation during operation
of the air conditioner, the self-clean operation is not performed.
(Unit stops.)
In the group opera-
tion, use this control
by connecting to
either header or
follower indoor unit.
10
Frequency fixed
operation (Test run)
<In case of wired remote controller>
1) When pushing [TEST] button for 4 seconds or more, [TEST]
is displayed on the display screen and the mode enters in
Test run mode.
2) Push [ON/OFF] button.
3) Using [MODE] button, set the mode to [COOL].
• Do not use other mode than [COOL] mode.
• During test run operation, the temperature cannot be
adjusted.
• An error is detected as usual.
• A frequency fixed operation is performed.
4) After the test run, push [ON/OFF] button to stop the operation.
(Display in the display part is same as the procedure in Item 1.)
5) Push [TEST] button to clear the test run mode.
([TEST] display in the display part disappears and the
status returns to the normal stop status.)
Command frequency
is approximately [S7]
<In case of wireless remote controller>
1) When TEMPORARY button is pushed for 10 seconds or
more, “Pi!” sound is heard and the operation changes to test
run. After approx. 3 minutes, a cooling operation starts
forcedly.
Check cool air starts blowing. If the operation does not start,
check wiring again.
2) To stop a test operation, push TEMPORARY button once
again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor units in test
run.
TEMPORARY button