No. Part name
Fan,
Fan case,
Quantity of fan
Shaft QTY
2
3
4
1. Detachment
1) Perform works of 1 of and .
2) Remove the
support plate.
(Ø4 x 10, 1 pcs.) (24-48 type only) The
screw on a front side is removed, and it
detaches it from the square hole on the
back side.
3) Remove the fixing screws of
the fan case (under).
(Ø4 x 10, 1 pcs.)
4) The hanging claw on both sides of fan
case (under) is removed.
5) Fan case (under) is pulled out from the
partition plate, and fan case (under) is
removed.
6) The screw with the hexagonal screw
hole to of the coupling is loosened, and
the shaft is removed with the fan.
7) The screw with the hexagonal screw
hole of the fan is loosened, and the fan
is detached from the shaft.
1) Perform works of 1 of , and .
2) Remove
connectors for fan motor wiring
from control P.C. board.
CN210 : Fan motor (5P, White)
3) Remove the fixing screws of
the fan case (under).
(Ø4 x 10, 1 pcs.)
4) The hanging claw on both sides of fan
case (under) is removed.
5) Fan case (under) is pulled out from the
partition plate, and fan case (under) is
removed.
6) Remove the fixing screws of the
fixing plate (2 pcs.) at the side of the fan
motor. (Ø5 x 10, 2 pcs.)
The earth screw is tightening together
with motor fixing screw.
7) While supporting the fan motor by
hands, remove the the fan motor.
8) The screw with the hexagonal screw
hole of the fan is loosened, and the fan
is detached from the shaft.
Remarks
13, 18
24, 25, 30
36, 39, 40, 48, 60
Model
Procedure
Square hole
Support plate
Front side screw
Hanging claw
Coupling
Shaft and Fan
FILE NO. SVM-19024